Plan Review Notes
Plan Review Notes For Permit 03111377
Permit Number 03111377
Review Stop E
Sequence Number 2
Notes
Date Text
2004-02-10 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE SEE THAT PLANS ARE NOW
 BEING SUBMITTED WITH A RISER DIAGRAM.
  
 2)NOTE: PLEASE SHOW GROUNDING EELCTRODE
 ETC FOR THE DEATCHED BLDG. PER 250.32
 FOOTER STEEL, COLD WATER. 250.50
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 4)NOTE: PLEASE HAVE PLANS SIGNED, DATED
 AND SEALED BY THE ARCH OF RECORD PER
 FS 481.221. PLANS ARE COPIES. MUST BE
 ORIGINAL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]