| Plan Review Notes For Permit 03111377 |
| Permit Number |
03111377 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-23 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT ELECTRICAL RISER | | | DIAGRAM WITH SERVICE.215.5 CONDUCTORS, | | | CONDUIT ETC. PANEL/SIZE ETC. | | | | | | 2)NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | SYSTEM FOR DETACHED BLDG. 250.32 | | | | | | 3)NOTE: PLEASE SEE THAT ALL RECEPTS IN | | | GARAGE TO MEET 210.8 (GFI) EXPT OF | | | OPENER/DEDICATED. | | | | | | 4)NOTE: PLEASE SUBMIT INFORMATION FOR | | | FEED FOR GARAGE SERVICE. | | | | | | PLEASE NOTE: DUE TO PLANS NOT BEING | | | COMPLETE AT THIS TIME, OTHER COMMENTS | | | MAY ARISE WHEN PLANS HAVE BEEN COMPLETED | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|