Plan Review Notes
Plan Review Notes For Permit 03111377
Permit Number 03111377
Review Stop B
Sequence Number 1
Notes
Date Text
2003-12-31 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03111377
 ADD: 700 S. OLIVE AVE.
 CONT: TRAMMELL CONST
 TEL: (904)334-5691
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 FIRST REVIEW
 ACTION: DENIED
  
 1) FIRE DISTRICT:
 NO TYPE VI CONSTRUCTION, SHEET A-3
 DETAIL"B" INDICATES WOOD STUDS AND PLY-
 WOOD SHEATHING NOT TO BE USED IN THE
 FIRE DISTRICT. F102.1.
  
 2) PLANS DO NOT INDICATE THE TYPE OF CON
 STRUCTION, TYPE VI NOT ALLOWED ,FIRE DIS
 TRICT, TABLE 600 REQUIRES A 3 HR WALL
 FOR TYPE V CONST. WHEN LOCATED LESS THAN
 3'-0" FROM THE PROPERTY LINE. SEE FOOT-
 NOTE "B".
  
 3) 2117.1.2 CATHEDRAL ENDWALLS.
 GABLE ENDWALLS ADJACENT TO CATHEDRAL
 CEILINGS SHALL BE CONTINIOUS FROM THE
 UPPERMOST FLOOR TO THE CEILING DIAPHRAM
 OR TO THE ROOF DIAPHRAM. THE MASONARY
 WALL CAN NOT STOP AT THE PROPOSED LOCA-
 TION.
  
 4)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A-3 DETAIL "C" INDICATES A 4-BAR
 BEAM, THE PLAN INDICATES A ARCH TO BE IN
 CORPORATED INTO THE BEAM, AT WHAT DEPTH
 IS THE BOTTOM STEEL TO BE PLACED? ALSO
 WILL THERE BE STIRRIPS OR HOOPS IN THIS
 BEAM? SIZE & WHAT SPACING?
  
 5) OCCUPANCY: STORAGE, 1027.1.1 SINGLE
 EXIT REQUIREMENTS (3) THE MAXIMUM DISTAN
 CE OF TRAVEL TO THE EXIT DOES NOT EX-
 CEED 50'.1012.1.2 EGRESS DOORS SHALL BE
 SIDE SWINGING TYPE.
  
 6)FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 7)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 8) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS: LOUVER
  
 A REPORT FOR SERIES 238 ALUM CASEMENT
 WINDOW IS INCLUDED IN THE PERMIT PACKAGE
 BUT NOT SHOWN ON PLAN.
  
 ALSO INCLUDED IN THE PACKAGE IS A REPORT
 FOR A SERIES 1000 8'-0" OUTSWING WOOD
 DOOR, PLAN CALLS FOR A 3'-10" WIDE DOOR
 BUT THE REPORT IS FOR 3'-0".
  
 9)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10) ENCLOSED PARKING GARAGES, MORE THAN
 (4) AUTOMOBILES OR TRUCKS OF 1 TON MAX.
 CAPACITY. 411.4.2 THE MECHANICAL SYSTEM
 SHALL BE CAPABLE OF PROVIDING 6 AIR
 CHANGES PER HR. UNDER NORMAL USE THE
 VENTILATION OF THE ENCLOSED AUTOMOBILE
 PARKING SHALL COMPLY WITH THE VENTILA-
 TION REQUIREMENTS 411.5.4.
  
 11)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026