| 2003-12-31 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03111377 |
| | ADD: 700 S. OLIVE AVE. |
| | CONT: TRAMMELL CONST |
| | TEL: (904)334-5691 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | FIRST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) FIRE DISTRICT: |
| | NO TYPE VI CONSTRUCTION, SHEET A-3 |
| | DETAIL"B" INDICATES WOOD STUDS AND PLY- |
| | WOOD SHEATHING NOT TO BE USED IN THE |
| | FIRE DISTRICT. F102.1. |
| | |
| | 2) PLANS DO NOT INDICATE THE TYPE OF CON |
| | STRUCTION, TYPE VI NOT ALLOWED ,FIRE DIS |
| | TRICT, TABLE 600 REQUIRES A 3 HR WALL |
| | FOR TYPE V CONST. WHEN LOCATED LESS THAN |
| | 3'-0" FROM THE PROPERTY LINE. SEE FOOT- |
| | NOTE "B". |
| | |
| | 3) 2117.1.2 CATHEDRAL ENDWALLS. |
| | GABLE ENDWALLS ADJACENT TO CATHEDRAL |
| | CEILINGS SHALL BE CONTINIOUS FROM THE |
| | UPPERMOST FLOOR TO THE CEILING DIAPHRAM |
| | OR TO THE ROOF DIAPHRAM. THE MASONARY |
| | WALL CAN NOT STOP AT THE PROPOSED LOCA- |
| | TION. |
| | |
| | 4)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | SHEET A-3 DETAIL "C" INDICATES A 4-BAR |
| | BEAM, THE PLAN INDICATES A ARCH TO BE IN |
| | CORPORATED INTO THE BEAM, AT WHAT DEPTH |
| | IS THE BOTTOM STEEL TO BE PLACED? ALSO |
| | WILL THERE BE STIRRIPS OR HOOPS IN THIS |
| | BEAM? SIZE & WHAT SPACING? |
| | |
| | 5) OCCUPANCY: STORAGE, 1027.1.1 SINGLE |
| | EXIT REQUIREMENTS (3) THE MAXIMUM DISTAN |
| | CE OF TRAVEL TO THE EXIT DOES NOT EX- |
| | CEED 50'.1012.1.2 EGRESS DOORS SHALL BE |
| | SIDE SWINGING TYPE. |
| | |
| | 6)FL BLDG 1909.3 (EXEPTION# 2) |
| | CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| | W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| | FABRIC LOCATED IN THE MIDDLE TO THE |
| | UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| | PORTED BY APPROVED MATERIALS OR SUPPORTS |
| | AT SPACING NOT TO EXCEED 3 FT OR IN |
| | ACCORDANCE WITH MANUFACTURER'S SPEC. |
| | |
| | 7)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 8) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: LOUVER |
| | |
| | A REPORT FOR SERIES 238 ALUM CASEMENT |
| | WINDOW IS INCLUDED IN THE PERMIT PACKAGE |
| | BUT NOT SHOWN ON PLAN. |
| | |
| | ALSO INCLUDED IN THE PACKAGE IS A REPORT |
| | FOR A SERIES 1000 8'-0" OUTSWING WOOD |
| | DOOR, PLAN CALLS FOR A 3'-10" WIDE DOOR |
| | BUT THE REPORT IS FOR 3'-0". |
| | |
| | 9)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 10) ENCLOSED PARKING GARAGES, MORE THAN |
| | (4) AUTOMOBILES OR TRUCKS OF 1 TON MAX. |
| | CAPACITY. 411.4.2 THE MECHANICAL SYSTEM |
| | SHALL BE CAPABLE OF PROVIDING 6 AIR |
| | CHANGES PER HR. UNDER NORMAL USE THE |
| | VENTILATION OF THE ENCLOSED AUTOMOBILE |
| | PARKING SHALL COMPLY WITH THE VENTILA- |
| | TION REQUIREMENTS 411.5.4. |
| | |
| | 11)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |