| Plan Review Notes For Permit 03111369 |
| Permit Number |
03111369 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-12 00:00:00 | ************* UNSAT ************ | | | | | | 1)NOTE: PLEASE SEE FS 481.221 FOR ALL | | | INFORMATION REQ'D ON TITLE BLOCK FOR | | | ARCH OF RECORD. PLEASE ALSO SEE FAC | | | 61G1-16.004 FOR ADDITIONAL INFORMATION | | | REQ'D. INCLUDING ADDRESS OF JOB. | | | IMPRESSION OF SEAL SHOULD BE CLEAR AND | | | VISABLE. | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATING FOR ALL | | | NEW EUIPMENT BEING INSTALLED. | | | MAINS/ BRKRS AND PANELS ARE ALLL TO BE | | | RATED FOR THE AVAIABLE FAULT CURRENT. | | | 110.9/215.5 | | | | | | PLEASE NOTE, INFORMATION FOR NOTE #1 IS | | | REQ'D ON ALL SHEETS AND NOT JUST THE | | | ELECTRICAL SHEETS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|