Plan Review Notes
Plan Review Notes For Permit 03111322
Permit Number 03111322
Review Stop E
Sequence Number 2
Notes
Date Text
2004-02-09 00:00:00*********UNSAT ************
  
 PLEASE ALSO SEE NOTES UNDER 03111319
  
 PLEASE SEE THE ONNLY CORRECTION THAT
 WAS MADE WAS COMPLETE SIGNATURE.
  
 NOTE: PLANS REQUIRE ADDRESS OF JOB.
 PLANS STILL REFERENCE 99 NEC. WE
 ARE UNDER 2002.
 PLANS STILL SHOW WIND LOADS FOR
 LIGHTS AND POLES AT 120 MPH. PLEASE SEE
 2001 FBC. WE ARE UNDER 140 MPH.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]