2003-12-15 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLANS REF 1999 NEC. WE AE UNDER
 2002 NEC AND WAS ADOPTED 7/1/2003.
 PLEASE CORRECT.
  
 2)NOTE: PLEASE SEE WIND LOADING FOR
 LIGHT POLES SHOWN AT 120MPH. WE ARE AT
 140 MPH. PLEASE SEE FBC FOR WINDLOADS.
  
 3)NOTE: PLEASE "SIGN" PLANS WITH A
 COMPLETE SIGNATURE AS REQ'D UNDER
 FS 471.025 AND FAC 61G15-23.002.
 PLEASE ALSO INCLUDE ALL LICENSE #'S
 TO CORRELATE WITH ENG OF RECORD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  