| Plan Review Notes For Permit 03111290 |
| Permit Number |
03111290 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-02-05 00:00:00 | DENIED | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) THE PRINT ON THE REVISED SHEETS IS | | | SMEARED AND HAS RUBBED OFF IN SEVERAL | | | PLACES. THE INK DOES NOT APPEAR TO BE | | | PERMANENT. PLEASE CORRECT. | | | | | | 3) THE UPLIFT GIVEN FOR THE USP RT24T | | | CONNECTOR ON A3 INCLUDES A ONE-THIRD | | | INCREASE IN THE STEEL CALCULATION. THIS | | | IS NOT ALLOWED BY FBC 1609.4.3. THE | | | VALUE SHOULD BE 1125#, SEE CURRENT USP | | | CATALOG. | | | | | | 4) PROVIDE DRAWINGS AND DETAILS FOR THE | | | CONSTRUCTION OF THE COVERED ENTRY PORCH | | | BETWEEN THE MAIN HOUSE AND GUEST HOUSE. | | | | | | 5) PROVIDE STRUCTURAL DETAILS OF THE | | | CANTILEVERED TRUSSES AT THE COVERED | | | PORCH AT THE FAMILY ROOM. | | | | | | 6) SPECIFY THE ROOF SHEATHING FASTENING | | | REQUIREMENTS. SEE CITY OF WPB AMENDMENTS | | | TO FBC TABLE 2306.1. SEE FBC 1606.2.3 | | | AND 1606.2(C). | | | | | | 7) SUBMIT PRODUCT APPROVALS FOR THE | | | SINGLE HUNG WINDOWS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|