Plan Review Notes
Plan Review Notes For Permit 03111290
Permit Number 03111290
Review Stop B
Sequence Number 1
Notes
Date Text
2004-01-06 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE GLASS BLOCK IN THE MASTER BATH
 SHOWER AND TUB ARE REQUIRED TO BE SAFETY
 GLASS PER FBC 2405.2.1. GLASS BLOCK WITH
 A UNIFORM FACE THICKNESS OF 0.25INCH IS
 EXEMPT PER FBC 2405.2.2. PLEASE SPECIFY
 THIS ON PLANS AND SUBMIT THE PROPER
 G.B. PRODUCT APPROVAL.
  
 3) REVISE THE NUMBER OF NAILS SPECIFIED
 FOR THE RT24T CONNECTOR ON A3. THE
 CORRECT AMOUNT OF NAILS IS (12) AND (14)
 EQUALLY DISTRIBUTED TO BOTH SIDES OF THE
 CONNECTION.
  
 4) SPECIFY THE LENGTH/EMBED DEPTH OF THE
 1/2" EXP. ANCHOR BOLTS FOR THE BEARING
 WALL ON A6.
  
 5) REVISE THE ROOF SHEATHING NOTES ON
 SHEET A6. THE MINIMUM THICKNESS FOR ROOF
 SHEATHING IS 19/32" PER CITY AMENDMENTS
 TO FBC TABLE 2309.3A.
  
 6) REVISE THE ROOF SHEATHING NOTES ON
 SHEETS A3 AND A6. THE CORNERS OF HIP
 ROOFS ARE ZONE 3 PER CITY AMENDMENTS TO
 FBC TABLE 2306.1. ALSO SEE FBC 1606.2.3
 AND 1606.2(C). THE ROOF SHEATHING IS
 REQUIRED TO BE NAILED AT 4"OC AT THE
 EDGES IN ZONE 3.
  
 7)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL FORM PER
 RULE 9B-72. SEE THE FORM ATTACHED.
  
 8) SUBMIT PRODUCT APPROVALS FOR THE
 GLASS BLOCK.
  
 9) REVISE SHEET A1 TO INDICATE THAT THE
 FRENCH DOORS W/SIDELITES AT THE LIVING
 ROOM IS AN ASSEMBLY AS INDICATED BY THE
 PRODUCT APPROVAL AND NOT A PAIR OF
 FRENCH DOORS WITH FIXED FRENCH DOORS ON
 EACH SIDE AS SHOWN ON THE PLAN.
 THERE ARE THREE SETS OF WINDLOAD
 PRESSURES LISTED ON THE PLANS. THERE
 SHOULD BE ONLY ONE SET OF PRESSURES IF
 THIS IS ONE OPENING. PLEASE CLARIFY.
  
 10) THE PRODUCT APPROVAL SUBMITTED FOR
 THE 2" HEAVY MULLIONS IS ONLY GOOD FOR
 + OR - 44PSF FOR THE MULLION ABOVE THE
 FRENCH DOOR W/SIDELITES AT THE L.R.
 WHICH SPANS 140". THIS DOES NOT MEET THE
 -45PSF LISTED ON THE PLANS FOR THIS
 OPENING. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714