| 2004-01-06 00:00:00 | DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE GLASS BLOCK IN THE MASTER BATH |
| | SHOWER AND TUB ARE REQUIRED TO BE SAFETY |
| | GLASS PER FBC 2405.2.1. GLASS BLOCK WITH |
| | A UNIFORM FACE THICKNESS OF 0.25INCH IS |
| | EXEMPT PER FBC 2405.2.2. PLEASE SPECIFY |
| | THIS ON PLANS AND SUBMIT THE PROPER |
| | G.B. PRODUCT APPROVAL. |
| | |
| | 3) REVISE THE NUMBER OF NAILS SPECIFIED |
| | FOR THE RT24T CONNECTOR ON A3. THE |
| | CORRECT AMOUNT OF NAILS IS (12) AND (14) |
| | EQUALLY DISTRIBUTED TO BOTH SIDES OF THE |
| | CONNECTION. |
| | |
| | 4) SPECIFY THE LENGTH/EMBED DEPTH OF THE |
| | 1/2" EXP. ANCHOR BOLTS FOR THE BEARING |
| | WALL ON A6. |
| | |
| | 5) REVISE THE ROOF SHEATHING NOTES ON |
| | SHEET A6. THE MINIMUM THICKNESS FOR ROOF |
| | SHEATHING IS 19/32" PER CITY AMENDMENTS |
| | TO FBC TABLE 2309.3A. |
| | |
| | 6) REVISE THE ROOF SHEATHING NOTES ON |
| | SHEETS A3 AND A6. THE CORNERS OF HIP |
| | ROOFS ARE ZONE 3 PER CITY AMENDMENTS TO |
| | FBC TABLE 2306.1. ALSO SEE FBC 1606.2.3 |
| | AND 1606.2(C). THE ROOF SHEATHING IS |
| | REQUIRED TO BE NAILED AT 4"OC AT THE |
| | EDGES IN ZONE 3. |
| | |
| | 7)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL FORM PER |
| | RULE 9B-72. SEE THE FORM ATTACHED. |
| | |
| | 8) SUBMIT PRODUCT APPROVALS FOR THE |
| | GLASS BLOCK. |
| | |
| | 9) REVISE SHEET A1 TO INDICATE THAT THE |
| | FRENCH DOORS W/SIDELITES AT THE LIVING |
| | ROOM IS AN ASSEMBLY AS INDICATED BY THE |
| | PRODUCT APPROVAL AND NOT A PAIR OF |
| | FRENCH DOORS WITH FIXED FRENCH DOORS ON |
| | EACH SIDE AS SHOWN ON THE PLAN. |
| | THERE ARE THREE SETS OF WINDLOAD |
| | PRESSURES LISTED ON THE PLANS. THERE |
| | SHOULD BE ONLY ONE SET OF PRESSURES IF |
| | THIS IS ONE OPENING. PLEASE CLARIFY. |
| | |
| | 10) THE PRODUCT APPROVAL SUBMITTED FOR |
| | THE 2" HEAVY MULLIONS IS ONLY GOOD FOR |
| | + OR - 44PSF FOR THE MULLION ABOVE THE |
| | FRENCH DOOR W/SIDELITES AT THE L.R. |
| | WHICH SPANS 140". THIS DOES NOT MEET THE |
| | -45PSF LISTED ON THE PLANS FOR THIS |
| | OPENING. PLEASE CORRECT. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |