Plan Review Notes
Plan Review Notes For Permit 03111280
Permit Number 03111280
Review Stop E
Sequence Number 5
Notes
Date Text
2004-11-01 00:00:00******* UNSAT ***************
  
 1)NOTE: PLEASE SEE OCP FOR AHU'S PER
 424.3B. SHOWS 50A ON 10+KW UNITS WITH
 #8.
 SOME SHOW #6, YET STILL HAVE 50A OCP.
  
 2)NOTE: PLEASE SEE SOME BRANCH CIRCUITS
 ARE SHOWN W/ 25A OCP ON #12.
 PLEASE SEE MAX OCP IS TO BE 20A.
 310.16/ NOTES ETC. 110.14/ 240.4
  
  
 *** PLEASE SEE PLUMB REVIEW COMMENTS
 FOR
 SEALED PHOTOCOPIES. (8 1/2X 11'S)
 ATTACHED TO PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.