| 2004-11-01 00:00:00 | ******* UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE OCP FOR AHU'S PER | | | 424.3B. SHOWS 50A ON 10+KW UNITS WITH | | | #8. | | | SOME SHOW #6, YET STILL HAVE 50A OCP. | | | | | | 2)NOTE: PLEASE SEE SOME BRANCH CIRCUITS | | | ARE SHOWN W/ 25A OCP ON #12. | | | PLEASE SEE MAX OCP IS TO BE 20A. | | | 310.16/ NOTES ETC. 110.14/ 240.4 | | | | | | | | | *** PLEASE SEE PLUMB REVIEW COMMENTS | | | FOR | | | SEALED PHOTOCOPIES. (8 1/2X 11'S) | | | ATTACHED TO PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO TWO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|