| Plan Review Notes For Permit 03111280 |
| Permit Number |
03111280 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-04-07 00:00:00 | PROVISO | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW PRIOR TO ROUGH INSPECTION. | | | | | | 1} SEE 700.12(E). EMERGENCY LIGHTS | | | STILL DO NOT COMPLY. MUST BE ON THE | | | SAME CIRCUIT THAT SERVES NORMAL LIGHTING | | | IN THE AREA. SEE SHEET #3. | | | | | | 2} THERE ARE BRANCH CIRCUIT NUMBERS | | | MISSING FROM SOME LIGHTING, SEE HALL ON | | | SHEET #5, ROOM 102 ALSO. | | | | | | 3} THE WATER COOLER AND COPIER CIRCUITS | | | ARE NOT MARKED CORRECTLY, SHEET #4. | | | PLEASE CHECK ALL BRANCH CIRCUIT #'S | | | | | | 4} INDICATE THE LOCATION OF PANEL "A". | | | | | | SEE FS 553.80(2)(B), ATTACHED. FEES DUE | | | BY STATUTE. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|