2004-04-07 00:00:00PROVISO
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW PRIOR TO ROUGH INSPECTION.
  
 1} SEE 700.12(E). EMERGENCY LIGHTS
 STILL DO NOT COMPLY. MUST BE ON THE
 SAME CIRCUIT THAT SERVES NORMAL LIGHTING
 IN THE AREA. SEE SHEET #3.
  
 2} THERE ARE BRANCH CIRCUIT NUMBERS
 MISSING FROM SOME LIGHTING, SEE HALL ON
 SHEET #5, ROOM 102 ALSO.
  
 3} THE WATER COOLER AND COPIER CIRCUITS
 ARE NOT MARKED CORRECTLY, SHEET #4.
 PLEASE CHECK ALL BRANCH CIRCUIT #'S
  
 4} INDICATE THE LOCATION OF PANEL "A".
  
 SEE FS 553.80(2)(B), ATTACHED. FEES DUE
 BY STATUTE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026