Plan Review Notes
Plan Review Notes For Permit 03111280
Permit Number 03111280
Review Stop P
Sequence Number 2
Notes
Date Text
2004-02-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) ALL TOILET ROOM SHALL SHOW CLEAR
 FLOOR SPACE PER SECTIONS 11-4.16.3,
 11-4.19.3, 11-4.22.3 & 11-4.24.5.
 2) DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQUIRED FOR ANY FIXTURE.
 11-4.22.2
 3) SHT 4 OF 7 ROOM 103 TOILET SHALL NOT
 ENTER INTO UNOBSTRUCTED TURNING AREA FOR
 TOILET ROOM.
 4) SHT 3 OF 7 SANITARY RISER DIAGRAM,
 SHOW ALL PIPE SIZE RISER. INFORMATIONAL
 NOTE: 5" PIPE IS NOT A COMMON PIPE SIZE.
 UP TO 36 FIXTURE UNITS CAN BE DRAINED ON
 3" SANITARY PIPE.
 5) SHT 3 OF 7 WATER RISER DIAGRAM. WATER
 HAMMER ARRESTORS SHALL BE INSTALLED AT
 THE DISHWASHER AND ICE MAKER, (IF INSTA-
 LLED), PER SECTION 604.9 LOCATED NEAR
 THE FIXTURE IN AN "EFFECTIVE RANGE" NOT
 IN CEILING. PDI-WH 201 AND MANUF. IN-
 STALLATION INSTRUCTIONS.
 6) SHT 3 OF 7 WATER RISER DIAGRAM, WATER
 HEATERS WILL REQUIRE THERMAL EXPANSION
 CONTROL PER 607.3.2 AND A VACUUM RELIEF
 VALVE PER 504.2.
 7) SHT 2 OF 7 ROOM 128 STAFF LOUNGE, THE
 WATER HEATER SHALL BE ACCESSIBLE. PROVI-
 DE DETAILS.
  
 REVIEW BY KEN STEVENS