Plan Review Notes
Plan Review Notes For Permit 03111280
Permit Number 03111280
Review Stop E
Sequence Number 2
Notes
Date Text
2004-01-29 00:00:00************** UNSAT **************
  
 ** PLEASE SEE NOTES ON PREVIOUS REVIEW**
  
 1)NOTE: PLEASE SHOW CIRCUITING FOR ALL
 EM/EXT LTS PER 700.12E.
 SOME NOT CORRECTED AND PANEL SCHEDULES
 ARE THE SAME SUBMITTED FIRST TIME.
  
 2)NOTE: PLEASE SEE THAT SIGN(S) CIRCUITS
 REQ'D PER 600.5 ARE NOW SHOWN ON PLANS,
 HOWEVER, PANEL SCHEDULES DO NOT REFLECT
 CHANGES.
  
 3)NOTE: PLEASE SEE THAT LICENSE #'(S)
 REQ'D ON TITLE BLOCKS PER 61G1-16
 ARE MISSING FROM ORIG SHEETS.
  
 ** PLEASE SEE BLDG REVIEW COMMENTS. PLAN
 -S STILL SHOW AN ADDRESS OF "OLD" OKEE-
 -CHOBEE. PLEASE CORRECT. PLANS ARE REQ'D
 TO LIST ADDRESS PER 61G1-16.004
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy