| Date |
Text |
| 2004-01-28 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03111280 |
| | ADD: 1806 OKEECHOBEE ROAD |
| | CONT: WINFREE CONTRACTING |
| | TEL: (561)744-6939 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | NOTE: ALL CORRESPONDANCE ABOUT THIS |
| | PARCEL SHOULD BE ADDRESSED AS OKEECHOBEE |
| | ROAD, THERE IS NO " OLD OKEECHOBEE ROAD" |
| | WITHIN THE COPARATE CITY LIMITS. THIS |
| | SAME ROAD WES1)OF FLORIDA MANGO (COUNTY) |
| | IS NAMED OLD OKEECHOBEE ROAD. |
| | WHEN THE REFRENCE OF OLD OKEECHOBEE |
| | IS USED IN 9-1-1 RESPONCE THEY WILL |
| | RESPOND TO THE ROAD WEST OF FLORIDA |
| | MANGO.! |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOWS |
| | B) MULLIONS |
| | C) EXTERIOR SWING DOORS |
| | D) OVERHEAD GARAGE DOORS |
| | E) STORM SHUTTERS |
| | *************IMPORTANT****************** |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | WINDOWS AND DOORS EVEN IF SHUTTERED |
| | SHALL SUPPLY PRODUCT TESTING REPORTS |
| | REQUIRED FOR WIND LOADS!!!!1606.2.4 |
| | MAIN FORCE RESISTING SYSTEM. |
| | |
| | 3)FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | 4)1707.4.5.1 MULLIONS OCCURRING |
| | BETWEEN INDIVIDUAL WINDOW AND GLASS |
| | DOOR ASSEMBLIES. TESTING REPORTS ARE |
| | REQUIRED BY AN APPROVED TESTING |
| | LABORATORY OR BE ENGINEERED. |
| | |
| | 5)1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| | ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| | TO THE ROUGH OPENING SUBTRATE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |