Plan Review Notes
Plan Review Notes For Permit 03111280
Permit Number 03111280
Review Stop P
Sequence Number 1
Notes
Date Text
2003-12-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) ALL CAPPED PLUMBING PIPES SHALL BE
 INSPECTED PRIOR TO COVERING. SEC 105.6
 2) IF TOILET FACILITIES ARE PROVIDED ON
 A SITE, THEN EACH SUCH PUBLIC OR COMMON
 USE TOILET FACILITY SHALL COMPLY WITH
 11-4.22. SECTION 11-4.1.1(6). SUBMIT A
 DETAIL FOR TOILET ROOMS SHOWING COMPLI-
 ANCE WITH 11-4.16, 11-4.19, 11-4.22 AND
 ALL SUBSECTIONS
 3) SHT 3 OF 7, ONLY THE FIXTURES WITHIN
 THE BATHROOM GROUPS SHALL CONNECT TO THE
 WET-VENTED HORIZONTL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. 909.1 - THE
 SINK FROM ROOM 128 SHALL CONNECT DOWN-
 STREAM OF THE TOILET ROOM FIXTURES.
 4) SINKS IN ROOMS 111 & 128 SHALL COMPLY
 WITH 11-4.24 AND ALL SUBSECTIONS. PROVI-
 DE DETAIL.
 5) 61G1-16.004(2) FIRM LICENSE NUMBER
 REQUIRED ON TITLE BLOCK. FS481.2055
 6) PROVIDE A WATER RISER DIAGRAM. SEC
 104.3.1.1(3).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]