Plan Review Notes
Plan Review Notes For Permit 03111280
Permit Number 03111280
Review Stop M
Sequence Number 1
Notes
Date Text
2003-12-19 00:00:00PROVISO:
 DUCT SMOKE DETECTORS REQUIRED.PLEASE
 PROVIDE DUCT SMOKE DETECTORS IN THE
 SUPPLY AIR DUCT PER 2001 FBC(M) 606.2.1.
  
 FAN SHUTDOWN SHALL HAVE NOTIFICATION TO
 ALARM/STROBE IN NORMALLY OCCUPIED AREAS
 PER NFPA 90A 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.