 BUILDING PLAN REVIEW
 PERMIT: 03111280
 ADD: 1806 OKEECHOBE ROAD
 CONT: WINFREE CONTRACTING
 TEL: (561)744-6939
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 FIRST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET 1 OF 7 INDICATES A NEW STORAGE
 ROOM, BUT SHEET2 NOR SHEET4 (PHASE 1 &
 2) INDICATE THIS AREA ON THEIR FLOOR
 PLANS?
  
 3) FLOOR PLANS DO NOT INDICATE WHAT OPEN
 INGS ARE EXISTING AND WHICH ARE NEW?
  
 4) SHEET 1 INDICATES THE NEW COLUMN AT
 DOOR"D", AT WHAT THEIGHT IS THE BEAM?
 THE DETAIL SHEET 4 INDICATES THE USE OF
 A LINTEL BUT NO MENTION OF BEARING ON
 THE EXISTING COLUMN?
 VARIOUS DOOR OR WINDOWS SHOW WHAT
 APPEARS TO BE BLOCK INFILL, NO MENTION
 OF HOW TO BE ATTACHED TO THE EXISTING
 STRUCTURE? NO MENTION OF FILLED CELLS?
  
 5) SHEET 1 DESIGN CRITERIA FOR NEW
 STORAGE ROOM:ASCE 7-98 IMPORTANCE FACTOR
 INDICATES THE WIND IMPORTANCE FACTOR OF
 .77 TO BE USED ON CATEGORY I (BUILDINGS)
 NOT ADDITONS. TYPE I BUILDINGS BEING:
 A) AGRICULTURE FACILITIES
 B) CERTAIN TEMPORARY FACILITIES
 C) MINOR STORAGE FACILITIES- STORAGE
 SHEDS NOT ATTACHED TO BUILDINGS
 RE-EVALUATE STORAGE SHED WITH AN IMPORT-
 ANCE FACTOR 0F 1.00.
  
 6) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) MULLIONS
 C) EXTERIOR SWING DOORS BOTH GLAZED OR
 NON-GLAZED
 D) OVERHEAD GARAGE DOOR
 E) STORM SHUTTERS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7)SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD.SITE SPECIFIC ENGINEERING
 WILL BE REQUIRED IF THE MANUFACTURER HAS
 NOT LISTED THEIR PRODUCT WITH THE STATE!
  
 8) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 9)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 10)1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE.
  
 11) PLAN DO NOT INDICATE WHAT TYPE OF
 BUCKS ARE TO BE USED, CAUTION:
 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 12) THE DESIGN PROFESSIONAL DOES NOT
 INDICATE THE ANCHORING OF THE BUCKS NOR
 THE WINDOWS AND DOORS:
 1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 13) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 14) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 15) RAMP: 11-4.8.5(HANDRAILS) IF A RAMP
 RUN HAS A RISE GREATER THAN 6" OR A
 HORIZONTAL PROJECTION GREATER THAN 72",
 THEN IT SHALL HAVE HANDRAILS ON BOTH
 SIDES.
  
 16)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL. SEE ROOMS 124 & 125.
  
 17) THERE IS NO DETAILS OF THE STAFF
 LOUNGE, 11-4.24.2 SINKS REQUIRED TO BE
 ACCESSIBLE TO BE MOUNTED WITH THE
 COUNTER NO HIGHER THAN 34 INCHES.
  
 18) 1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  