| Plan Review Notes For Permit 03111252 |
| Permit Number |
03111252 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-03-05 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)A NOTE WAS ENCLOSED INDICATING THAT | | | YOU WANTED FOR THIS PROJECT TO BE A | | | MASTER.THIS MUST BE DONE ON A SEPARATE | | | APPLICATION.SUBMIT TWO COPIES OF | | | DRAWINGS WITH AN APPLICATION. | | | | | | 2.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE | | | STAMPED AND THE RECEIPT ATTACHED TO THE | | | APPLICATION.233-5025 | | | | | | 3.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 4.)GENZ ENGINEERING MUST HAVE AN | | | AUTHORIZATION NUMBER FROM THE BOARD OF | | | PROFESSIONAL ENGINEERS TO PRACTICE | | | ENGINEERING.THIS NUMBER MUST BE ON | | | EACH SHEET. | | | | | | 5.)FLOOR PLAN NOTE 4 (4.1) SHOWS 4.2 | | | INSULATION; R5 REQUIRED PER ENERGY CALC. | | | | | | 6.)ATTIC ACCESS MINIMUM SIZE IS 20X36 | | | FBC2309.6. | | | | | | 7.)THE SIMONTON 435 WINDOW IS NOT | | | LISTED ON FLORIDA PRODUCT APPROVAL | | | NUMBER 204. | | | | | | 8.)PROVIDE A COPY OF THE TEST REPORT | | | FOR THE MASONITE DOORS. | | | | | | 9.)SEPARATE PERMITS REQUIRED. |
|