| Date |
Text |
| 2003-12-17 00:00:00 | DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) FBC* 1804.2.2AREA OF QUESTIONABLE |
| | SOIL.SUBMIT A GEOTECHNICAL REPORT |
| | TO VERIFY THE SAFE BEARING CAPACITY OF |
| | THE SOIL. |
| | |
| | 4) SAFETY GLAZING IS REQUIRED WITHIN |
| | 3' HORIZONTALLY OF A TUB OR SHOWER PER |
| | FBC 2405.2. SPECIFY ON THE PLANS THAT |
| | WINDOW (U) BESIDE THE TUB IN THE SECOND |
| | FLOOR BATH #2 IS TEMPERED. |
| | |
| | 5) SPECIFY THE FASTENERS (LENGTH/EMBED) |
| | FOR ATTACHING THE TRUSS BUCKETS TO THE |
| | WALL. SEE SHEET A7. |
| | |
| | 6) INDICATE ON THE COLUMN BASE DETAILS |
| | ON A7 TO REFER TO THE DETAIL ON A13 FOR |
| | ANCHORING DETAIL. |
| | |
| | 7) FBC 1015.3 REQUIRES THE BOTTOM RAIL |
| | ON A GUARDRAIL TO REJECT A 2" SPHERE. |
| | PLEASE CORRECT THE RAILING DETAIL ON A12 |
| | |
| | 8) THE WALL SECTIONS ON A12 SPECIFY A |
| | ATTIC INSULATION WITH A MINIMUM OF R-30 |
| | AND THE ENERGY CALCS. LISTS R-19. |
| | PLEASE CORRECT. |
| | |
| | 9) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL PER FAC |
| | RULE 9B-72. SEE FORM ATTACHED. |
| | |
| | 10) THE DESIGN PRESSURES ON THE PRODUCT |
| | APPROVAL FOR THE OVERHEAD GARAGE DOOR |
| | DOES NOT MEET THE PRESSURES LISTED ON |
| | THE PLANS. |
| | |
| | 11) THE PRODUCT APPROVAL SUBMITTED FOR |
| | THE GLAZED EXTERIOR DOOR IS FOR A DOOR |
| | WITH SIDELITES, THE DOOR ON THE PLANS |
| | DOES NOT HAVE SIDELITES. SUBMIT THE |
| | APPROPRIATE PRODUCT APPROVAL. NOTE THE |
| | ONE SUBMITTED DOES NOT MEET THE REQUIRED |
| | PRESSURES LISTED IN THE SCHEDULE ON A1. |
| | |
| | 12) THE KEY PLAN AND SCHEDULE SUBMITTED |
| | FOR THE STORM PANELS DOES NOT MATCH THE |
| | PLANS (SECOND FLOOR). SUBMIT REVISED |
| | KEY AND SCHEDULE. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |