Plan Review Notes
Plan Review Notes For Permit 03111167
Permit Number 03111167
Review Stop P
Sequence Number 1
Notes
Date Text
2003-12-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLA. ADMIN CODE
 FLA. STATUTES
  
 1) APPLICATION CALLS FOR HOOK UP FOR 2
 W/C'S - 2 LAV'S AND BAR SINK HOOK UP.
 THERE IS ALSO A BATHROOM WITH A W/C, TUB
 SHOWER AND TWO LAV'S THAT WILL HAVE TO
 BE ACCESSIBLE. SUBMIT DETAIL FOR THIS
 BATHROOM SHOWING COMPLIANCE WITH SECTION
 11-4.23 AND ALL SUBSECTIONS.
 2) KITCHENETTE SHALL COMPLY WITH SECTION
 11-4.24 AND ALL SUBSECTIONS. SUBMIT A
 DETAIL.
 3) ONLY ONE SET OF PLANS HAS BEEN SUB-
 MITTED FOR REVIEW. TWO SETS OF PLANS
 SHALL BE SUBMITTED FOR REVIEW. 104.2.1
 4) PLANS SHALL BE SIGNED, SEALED AND
 DATED BY THE ENGINEER OF RECORD. FAC
 61G15-23.002(1).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]