2005-06-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03111164
 ADD: 131 CORTEZ
 CONT: MARION CONSTRUCTION
 TEL: (561)662-3814
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION
  
 ACTION: DENIED
  
 1) SABANA WINDOWS IS NOT LISTED ON THE
 FL STATE WEB SITE,
 WWW,"FLORIDABUILDING.ORG", A LOCAL
 PRODUCT APPROVAL WILL BE REQUIRED .
  
 2) THERE IS CUT SHEETS INDICATING USE OF
 A HORIZONTAL MULLION. THERE IS NO
 INDICATION OF MULLIONS BEING TESTED IN
 EITHER THE WINDOW OR DOOR REPORT.
  
 3) MULLIONS:
 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 4)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.