| 2005-06-02 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 03111164 | | | ADD: 131 CORTEZ | | | CONT: MARION CONSTRUCTION | | | TEL: (561)662-3814 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISION | | | | | | ACTION: DENIED | | | | | | 1) SABANA WINDOWS IS NOT LISTED ON THE | | | FL STATE WEB SITE, | | | WWW,"FLORIDABUILDING.ORG", A LOCAL | | | PRODUCT APPROVAL WILL BE REQUIRED . | | | | | | 2) THERE IS CUT SHEETS INDICATING USE OF | | | A HORIZONTAL MULLION. THERE IS NO | | | INDICATION OF MULLIONS BEING TESTED IN | | | EITHER THE WINDOW OR DOOR REPORT. | | | | | | 3) MULLIONS: | | | 1707.4.5.1 MULLIONS OCCURRING | | | BETWEEN INDIVIDUAL WINDOW AND GLASS | | | DOOR ASSEMBLIES. TESTING REPORTS ARE | | | REQUIRED BY AN APPROVED TESTING | | | LABORATORY OR BE ENGINEERED. | | | | | | 4)1707.4.5.2 MULLIONS SHALL BE DESIGN- | | | ED TO TRANSFER THE DESIGN PRESSURE LOADS | | | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES | | | TO THE ROUGH OPENING SUBTRATE. |
|