2004-01-23 00:00:00************ PROVISO/ NOTES ************
 THE FOLLOWING IS ONLY BASED ON ALL
 OTHER REVIEWS PASSING. IF PLANS GO BACK
 FOR COMMENTS FOR ANY OTHER TRADES, PLANS
 NEED TO BE CORRETCED.
  
  
 1)NOTE: PLEASE SEE LOAD CALCULATIONS,
 SHOWS ALL AHU'S AT 10KW, HOWEVER PANEL
 SCHEDULE SHOWS AHU# 4 W/ 45A OCP.
 PLEASE SEE 424.3B FOR MIN OCP 125%.
  
 2)NOTE: PLEASE LIST THE REQ'D ARC FAULT
 ON PANEL SCHEDULE(S) AS REQUESTED ON
 PREVIOUS REVIEW. 210.12
  
 3)NOTE: PLEASE LIST REQ'D DEDICATED
 BATH(S) CIRCUIT(S) ON PANEL SCHEDULE.
 REQUESTED ON FIRST REVIEW. 210.11C3
 210.52D
  
 PLEASE SUBMIT THIS AND ALL OTHER
 REVISIONS BEFORE ROUGH INSPECTION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  