Plan Review Notes
Plan Review Notes For Permit 03111164
Permit Number 03111164
Review Stop E
Sequence Number 1
Notes
Date Text
2003-12-10 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE SEE NFPA-72 8-1.4.2
 SD'S ARE REQD' IN SIDE AND OUTSIDE ALL
 SLEEPING ROOMS. EACH LEVEL OF A MULTI-
 -LEVEL DWELLING AND IN THE VICINITY OF
 STAIRWAYS.
  
 2)NOTE: PLEASE SEE 210.52 FOR A COUPLE
 OF MISSING RECEPTS.
  
 3)NOTE: PLEASE SEE 210.8A6 FOR ALL
 RECEPTS SERVING KITCHEN COUNTERSPACE TO
 BE GFI/GFI PROTECTED. PLEASE SHOW OR
 INDICATE.
  
 4)NOTE: PLEASE SUBMIT COMPLETE PANELS
 SCHEDULES SHOWING ALL MIN REQ'D CIRCUITS
 PER 210.52,210.11,210.12, ETC ETC.
 PLEASE SHOW OCP , AWG ALSO.
  
 5)NOTE: PLEASE HAVE PLANS SIGNED, DATED
 AND SEALED BY THE ARCH OF RECORD PER
 FS 481.221 AND FAC 61G1-16
  
 6)NOTE: PLEASE SHOW ALL CONDUCTOR SIZES
 ON RISER DIAGRAM. 310.16/215.5
  
 7)NOTE: PLEASE SEE THAT "SERVICE" SIZE
 IS INDICATED AT 450A'S AND ONLY SHOWS
 A 400A METERCAN. PLEASE ADJUST.
  
 8)NOTE: PLEASE SUBMIT SPECS/ MANF INFO
 ON TRANSFER SWITCH AND HOW SWITCHING
 WILL BE. 230.74,230.75,230.82 ETC.
  
 9)NOTE: PLEASE SEE THAT TRANSFER SWITCH,
 CONDUCTORS,GUTTER, AND MAINS MAY NOT BE
 INSTALLED AS SHOWN. IF SERVICE STAYS
 "AS-IS" THEN A MAIN W/ OCP WOULD BE
 REQ'D INFRONT OF TANSFER SW. IF THIS IS
 NOT GOING TO BE DONE THEN PLEASE ADJUST/
 RECONFIGURE SERVICE.
 240.21, 230.76, 230.79,230.42 ETC.
  
 10)NOTE: PLEASE AIC RATINGS FOR ALL NEW
 EQUIPMENT BBEING INSTALLED. MAINS, BRKRS
 PANELS ARE ALL TO BE RATED FOR THE AVAIL
 -ABLE FAULT CURRENT. 110.9/215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
2003-12-09 00:00:00NOTES TO FOLLOW