| Date |
Text |
| 2003-12-10 00:00:00 | ***************** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE NFPA-72 8-1.4.2 |
| | SD'S ARE REQD' IN SIDE AND OUTSIDE ALL |
| | SLEEPING ROOMS. EACH LEVEL OF A MULTI- |
| | -LEVEL DWELLING AND IN THE VICINITY OF |
| | STAIRWAYS. |
| | |
| | 2)NOTE: PLEASE SEE 210.52 FOR A COUPLE |
| | OF MISSING RECEPTS. |
| | |
| | 3)NOTE: PLEASE SEE 210.8A6 FOR ALL |
| | RECEPTS SERVING KITCHEN COUNTERSPACE TO |
| | BE GFI/GFI PROTECTED. PLEASE SHOW OR |
| | INDICATE. |
| | |
| | 4)NOTE: PLEASE SUBMIT COMPLETE PANELS |
| | SCHEDULES SHOWING ALL MIN REQ'D CIRCUITS |
| | PER 210.52,210.11,210.12, ETC ETC. |
| | PLEASE SHOW OCP , AWG ALSO. |
| | |
| | 5)NOTE: PLEASE HAVE PLANS SIGNED, DATED |
| | AND SEALED BY THE ARCH OF RECORD PER |
| | FS 481.221 AND FAC 61G1-16 |
| | |
| | 6)NOTE: PLEASE SHOW ALL CONDUCTOR SIZES |
| | ON RISER DIAGRAM. 310.16/215.5 |
| | |
| | 7)NOTE: PLEASE SEE THAT "SERVICE" SIZE |
| | IS INDICATED AT 450A'S AND ONLY SHOWS |
| | A 400A METERCAN. PLEASE ADJUST. |
| | |
| | 8)NOTE: PLEASE SUBMIT SPECS/ MANF INFO |
| | ON TRANSFER SWITCH AND HOW SWITCHING |
| | WILL BE. 230.74,230.75,230.82 ETC. |
| | |
| | 9)NOTE: PLEASE SEE THAT TRANSFER SWITCH, |
| | CONDUCTORS,GUTTER, AND MAINS MAY NOT BE |
| | INSTALLED AS SHOWN. IF SERVICE STAYS |
| | "AS-IS" THEN A MAIN W/ OCP WOULD BE |
| | REQ'D INFRONT OF TANSFER SW. IF THIS IS |
| | NOT GOING TO BE DONE THEN PLEASE ADJUST/ |
| | RECONFIGURE SERVICE. |
| | 240.21, 230.76, 230.79,230.42 ETC. |
| | |
| | 10)NOTE: PLEASE AIC RATINGS FOR ALL NEW |
| | EQUIPMENT BBEING INSTALLED. MAINS, BRKRS |
| | PANELS ARE ALL TO BE RATED FOR THE AVAIL |
| | -ABLE FAULT CURRENT. 110.9/215.5 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| 2003-12-09 00:00:00 | NOTES TO FOLLOW |