Plan Review Notes
Plan Review Notes For Permit 03111139
Permit Number 03111139
Review Stop B
Sequence Number 3
Notes
Date Text
2004-02-12 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 A) MODIFIED BITUMEN ROOF SYSTEM. PAGE 15
 OF THE SUBMITTED MIAMI-DADE PRODUCT
 APPROVAL NOA# 01-0524.13 STATES THAT THE
 MAXIMUM DESIGN PRESSURE IS -45 PSF AND
 REFERS TO GENERAL LIMITATION #9
 (PAGE 23) WHICH DOES NOT PERMIT RATIONAL
 ANALYSIS OR EXTRAPOLATION FOR ENHANCED
 FASTENINGS AT PERIMETERS AND CORNERS.
 THE UPLIFT PRESSURES ON THE ROOF FRAMING
 PLAN (SHEET S-2.0) EXCEED THE MAX DESIGN
 PRESSURE.SUBMIT A PRODUCT APPROVAL FOR
 A ROOFING SYSTEM WITH SUFFICIENT UPLIFT
 CAPACITY.NOTE THAT THE ROOFING SYSTEM
 IS REQUIRED BE CLASS A OR B AS THE
 BUILDING IS IN THE FIRE DISTRICT.
  
 B) BARREL ALHAMBRA CLAY TILE.FROM THE
 SUBMITTED MIAMI-DADE PRODUCT APPROVAL
 NOA# 02-0603.04 IT IS NOTED THAT THE
 PROPOSED TILE REQUIRES ADHESIVE SET OR
 MORTAR SET ATTACHMENT.THEREFOR THE
 UNDERLAYMENT WILL BE REQUIRED TO RESIST
 THE UPLIFT PRESSURES STATED ON THE ROOF
 FRAMING PLAN (SHEET S-2.0).SEE COMMENT
 (A) ABOVE.
  
 C) ALUMINUM STOREFRONT.THE SUBMITTED
 MIAMI-DADE PRODUCT APPROVALS
 NOA# 02-1011.03 AND 02-1011.04 WERE
 MISSING DRAWING SHEETS 1 TO 8 AND 1 TO 6
 RESPECTIVELY, THESE HAVE BEEN PRINTED
 FROM THE MIAMI-DADE WEBSITE AT
 WWW.MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH
 _APP.ASP AND INSERTED.BY REFERING TO
 DRAWING SHEET 1 IT IS NOTED THAT THE
 ROUGH OPENING HEIGHTS AT DOOR TYPES I,
 IV, V AND VI ALL EXCEED THE MAXIMUM
 HEIGHT ALLOWED BY THE PRODUCT APPROVAL.
 ALSO, THE WIDTHS OF WINDOW TYPES B, C,
 D AND E ALL EXCEED THE MAXIMUM WIDTH
 (VERTICAL MULLION SPACING) ALLOWED BY
 THE PRODUCT APPROVAL.SUBMIT A PRODUCT
 APPROVAL FOR A STOREFRONT/FIXED WINDOW
 SYSTEM THAT IS APPLICABLE TO THE OPENING
 SIZES PROPOSED.
  
 D) HOLLOW METAL DOORS AND FRAMES.THE
 DOCUMENT SUBMITTED FOR PRODUCT APPROVAL
 APPEARS TO BE A CECO DOOR PRODUCTS
 DOCUMENT BEING USED TO CERTIFY DOORS
 MANUFACTURED BY CECO DOOR PRODUCTS.
 FL. ADMIN CODE RULE 9B-72 REQUIRES THAT
 AN APPLICATION FOR PRODUCT APPROVAL
 INCLUDE THE NAME, ADDRESS, REPORTS AND
 REPORT NUMBERS OF THE TESTING ENTITY,
 THE EVALUATION ENTITY OR THE
 CERTIFICATION ENTITY.THAT INFORMATION/
 DOCUMENTATION HAS NOT BEEN PROVIDED.
  
 NOTE:
  
 THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE, TO IDENTIFY
 WHICH PRODUCT OPTIONS/MATERIALS/SIZES
 ARE TO BE USED.
  
 FOR PRODUCTS WHICH DO NOT HAVE STATEWIDE
 PRODUCT APPROVAL, LOCAL PRODUCT APPROVAL
 CAN BE ACHIEVED IF THERE IS A QUALITY
 ASSURANCE PROGRAM IN PLACE WITH A STATE
 APPROVED QUALITY ASSURANCE ENTITY.IF
 NEITHER IS APPLICABLE, THEN SITE
 SPECIFIC APPROVAL IS REQUIRED.LOCAL
 PRODUCT APPROVAL WILL ALLOW A PRODUCT TO
 BE USED, IN ACCORDANCE WITH THE TEST
 CRITERIA, THROUGHT THE JURISDICTION OF
 WEST PALM BEACH.SITE SPECIFIC PRODUCT
 APPROVAL WILL ALLOW A PRODUCT TO BE
 USED ONLY ON THE PROJECT FOR WHICH THAT
 SITE SPECIFIC APPROVAL IS GRANTED.
 LOCAL AND SITE SPECIFIC PRODUCT APPROVAL
 APPLICATION FORMS ARE AVAILABLE FROM
 THIS OFFICE.APPROVED QUALITY ASSURANCE
 ENTITIES ARE LISTED ON THE DCA WEBSITE:
 WWW.FLORIDABUILDING.ORG/COMMON/C_ORG_
 REGI_SRCH.ASP
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS