2003-12-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) PROVIDE INFORMATION AND DETAIL FOR
 UPPER ROOFS ON SHT A1.0 SHOWING PRIMARY
 AND SECONDARY ROOF DRAINS, ROOF SIZE
 AND 1/2 AREA OF PARAPET WALLS, DRAIN
 SIZE ECT. SECTIONS 1106, AND 1107 AND
 ALL SUBSECTIONS.
 2) 3" SECONDARY DRAIN SHOWN ON SHT A1.0
 ARE NOT ACCEPTABLE. SECTION 1107.3 -
 MINIMUM OPENING FOR OVERFLOW SCUPPERS
 SHALL BE 3 TIMES THE CROSS SECTIONAL
 AREA OF PRIMARY DRAINS. (22"). THE
 OVERFLOW SCUPPER WILL HAVE TO BE A
 MINIMUM OF 6", OR A 6X4 RETANGLE.
 3) SEPARATE PLANS/PERMIT REQUIRED FOR
 FOUNTAIN. SHOW WATER SUPPLY, DRAIN, AND
 OVERFLOW LINES FOR FOUNTAIN. 104.2.1
 4) ENGINEER'S SIGNATURE REQUIRED ON SEAL
 PER FAC 61G15-23.002(1) & FS 471.025
 INITALS ON ACCEPTABLE PER FBPE & BLDG.
 OFFICIAL.
  