| Plan Review Notes For Permit 03111139 |
| Permit Number |
03111139 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-13 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FLA. ADMIN. CODE | | | FLA. STATUTES | | | | | | 1) PROVIDE INFORMATION AND DETAIL FOR | | | UPPER ROOFS ON SHT A1.0 SHOWING PRIMARY | | | AND SECONDARY ROOF DRAINS, ROOF SIZE | | | AND 1/2 AREA OF PARAPET WALLS, DRAIN | | | SIZE ECT. SECTIONS 1106, AND 1107 AND | | | ALL SUBSECTIONS. | | | 2) 3" SECONDARY DRAIN SHOWN ON SHT A1.0 | | | ARE NOT ACCEPTABLE. SECTION 1107.3 - | | | MINIMUM OPENING FOR OVERFLOW SCUPPERS | | | SHALL BE 3 TIMES THE CROSS SECTIONAL | | | AREA OF PRIMARY DRAINS. (22"). THE | | | OVERFLOW SCUPPER WILL HAVE TO BE A | | | MINIMUM OF 6", OR A 6X4 RETANGLE. | | | 3) SEPARATE PLANS/PERMIT REQUIRED FOR | | | FOUNTAIN. SHOW WATER SUPPLY, DRAIN, AND | | | OVERFLOW LINES FOR FOUNTAIN. 104.2.1 | | | 4) ENGINEER'S SIGNATURE REQUIRED ON SEAL | | | PER FAC 61G15-23.002(1) & FS 471.025 | | | INITALS ON ACCEPTABLE PER FBPE & BLDG. | | | OFFICIAL. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|