| Plan Review Notes For Permit 03111139 |
| Permit Number |
03111139 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-09 00:00:00 | PROVISO: PERMIT IS FOR THE SHELL ONLY | | | | | | PLEASE NOTE, PLAN SHEET M-1 DETAIL C.U. | | | SUPPORT DETAIL INDICATES 18". 18" SHALL | | | BE FROM THE ROOF SURFACE TO THE BOTTOM | | | OF THE SUPPORT RAIL. | | | | | | FRESH AIR INTAKES SHALL BE A MINIMUM OF | | | 10 FT FROM EXHAUST. | | | | | | PLEASE PROVIDE EQUIPMENT SCHEDULE & O.A | | | AND ENERGY CALCULATIONS WITH PERMIT | | | APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|