| 2004-01-05 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) IMPACT FEES. THE PLANS SHALL BE TAKEN |
| | TO PALM BEACH COUNTY BUILDING DEPARTMENT |
| | FOR IMPACT FEE ASSESSMENT. THEY SHALL BE |
| | STAMPED AT THAT OFFICE AND A COPY OF THE |
| | PAID RECEIPT SUBMITTED TO THE CITY OF |
| | WEST PALM BEACH DEPT OF CONSTRUCTION |
| | SERVICES BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) THE SUBMITTED SITE SURVEY STATES THE |
| | PROPERTY ADDRESS AS 5709 S. DIXIE HWY. |
| | AMEND TO 5705 S. DIXIE HWY. |
| | |
| | 3) THE PROPOSED BUILDING STRUCTURE |
| | TRANSGRESSES LEGAL BOUNDARY LINES |
| | BETWEEN THE LOTS WHICH COMBINE TO FORM |
| | 'THE SITE'.SUBMIT A COPY OF THE 'UNITY |
| | OF TITLE' DOCUMENT SO THAT FBC TABLE 600 |
| | BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| | NOT APPLICABLE. |
| | |
| | 4) FBC 11-4.6.3SHEET A-1.0RAMPS FROM |
| | ACCESSIBLE PARKING TO SIDEWALK.CURB |
| | RAMPS MUST BE LOCATED OUTSIDE OF THE |
| | PARKING ACCESS AISLE.THE RAMP AS SHOWN |
| | ENCROACHES ON THE 5' WIDE PARKING ACCESS |
| | AISLE.AMEND THE PLAN. |
| | |
| | 5) FBC 13-101.1.6SHELL BUILDINGS. |
| | THE WHOLE BUILDING (INCL. FUTURE TENANT |
| | SPACE) SHALL BE CONSIDERED.SHELL |
| | BUILDINGS SHALL BE SHOWN TO COMPLY WITH |
| | METHOD B (SEE SUB-CHAPTER 4).ALL |
| | ASSUMPTIONS MADE ABOUT SYSTEMS, NOT |
| | SHOWN ON THE CURRENT PLANS, SHALL BE |
| | LISTED AND APPENDED TO THE FORM 400B FOR |
| | SUBMITTAL.THIS WILL BE COMPARED TO THE |
| | ACTUAL SYSTEMS PROPOSED, AT A LATER, FOR |
| | INSTALLATION BY THE TENANT(S).THE |
| | ASSUMPTIONS LISTED ON THE APPENDIX SHEET |
| | SHALL BE AT LEAST THE MINIMUM STANDARD |
| | (LIGHTING, HVAC ETC) TO ALLOW THE WHOLE |
| | BUILDING TO BE OCCUPIED FOR IT'S |
| | INTENDED PURPOSE. |
| | |
| | 6) FBC 13-103.1.2THE SUBMITTED ENERGY |
| | CODE COMPLIANCE FORMS WERE NOT SIGNED |
| | BY EITHER THE BUILDING OWNER, THE |
| | OWNER'S ARCHITECT OR OTHER AUTHORIZED |
| | AGENT LEGALLY DESIGNATED BY THE OWNER. |
| | ALSO THE ARCHITECT'S REGISTRATION NUMBER |
| | WAS NOT ENTERED ON SHEET TWO.ADDRESS |
| | THESE ITEMS TOGETHER WITH COMMENT 5. |
| | |
| | 7) FBC 1403.3MASONRY VENEER.ANNOTATE |
| | THE PLANS GIVE THE SPECIFICATION FOR |
| | ATTACHMENT OF THE MASONRY VENEER. |
| | |
| | 8) FBC 2309.7ATTIC VENTILATION. |
| | SHEET A-5.0, SECTION 1.ATTIC SPACE |
| | SHALL BE VENTILATED. AMEND THE "UNVENTED |
| | ATTIC" ANNOTATION ON SECTION 1. |
| | |
| | 9) SHEET S-2.2, DETAIL 10, TYPICAL WALL |
| | SECTION AT ROOF EAVES.THE STATED |
| | 1515 LB UPLIFT CAPACITY OF THE HETAL 16 |
| | TRUSS ANCHOR EXCEEDS THE UPLIFT GIVEN IN |
| | THE 2003 SIMPSON CATALOGUE FOR 1-PLY |
| | TRUSS APPLICATION.AMEND THE DETAIL. |
| | |
| | 10) SHEET S-2.2, DETAIL 12, GIRDER TRUSS |
| | CONNECTION TO STEEL BEAM.THE STATED |
| | 2310 LB UPLIFT CAPACITY OF THE LTTI31 |
| | TENSION TIE EXCEEDS THE UPLIFT GIVEN IN |
| | THE 2003 SIMPSON CATALOGUE.AMEND THE |
| | DETAIL. |
| | |
| | 11) FBC 704.3SHEET S-2.2, DETAILS 4, 6 |
| | AND 7.SUBMIT JUSTIFICATION (UL LISTING |
| | OR EQUIVALENT) FOR THE PROPOSED USE OF |
| | 2X8 FIRE TREATED PLATE IN THE TENANT |
| | FIRE SEPARATION WALL OR AMEND THE DETAIL |
| | |
| | 12) FBC 1606.1.7WIND LOAD.THE PLANS |
| | SHALL STATE EXTERIOR COMPONENT AND |
| | CLADDING DESIGN WIND PRESSURES FOR THE |
| | DOORS AND WINDOWS AND FOR THE ROOF. |
| | |
| | 13) FBC* 2306.1ROOF SHEATHING NAIL |
| | SPACING.AMEND THE PLANS TO SPECIFY |
| | THE FASTENER TYPE AND SPACING. |
| | |
| | 14) SUBMIT PRODUCT APPROVALS FOR THE |
| | WINDOWS, EXTERIOR DOORS AND ROOF. |
| | NOTE: FL. ADMIN CODE RULE 9B-72 (IN |
| | EFFECT SINCE OCTOBER 1, 2003) REQUIRES |
| | THAT PRODUCTS HAVE STATEWIDE, LOCAL OR |
| | SITE-SPECIFIC PRODUCT APPROVAL.THE |
| | SUBMITTAL SHOULD INCLUDE THE STATEWIDE |
| | PRODUCT APPROVAL NUMBER (FL###), |
| | AVAILABLE FROM THE DEPT OF COMMUNITY |
| | AFFAIRS PRODUCT APPROVAL WEBSITE |
| | WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP |
| | |
| | 15) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| | ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| | OLD SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHALL BE INCLUDED WITH THE |
| | RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |