Plan Review Notes
Plan Review Notes For Permit 03111139
Permit Number 03111139
Review Stop B
Sequence Number 1
Notes
Date Text
2004-01-05 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 2) THE SUBMITTED SITE SURVEY STATES THE
 PROPERTY ADDRESS AS 5709 S. DIXIE HWY.
 AMEND TO 5705 S. DIXIE HWY.
  
 3) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.SUBMIT A COPY OF THE 'UNITY
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
 4) FBC 11-4.6.3SHEET A-1.0RAMPS FROM
 ACCESSIBLE PARKING TO SIDEWALK.CURB
 RAMPS MUST BE LOCATED OUTSIDE OF THE
 PARKING ACCESS AISLE.THE RAMP AS SHOWN
 ENCROACHES ON THE 5' WIDE PARKING ACCESS
 AISLE.AMEND THE PLAN.
  
 5) FBC 13-101.1.6SHELL BUILDINGS.
 THE WHOLE BUILDING (INCL. FUTURE TENANT
 SPACE) SHALL BE CONSIDERED.SHELL
 BUILDINGS SHALL BE SHOWN TO COMPLY WITH
 METHOD B (SEE SUB-CHAPTER 4).ALL
 ASSUMPTIONS MADE ABOUT SYSTEMS, NOT
 SHOWN ON THE CURRENT PLANS, SHALL BE
 LISTED AND APPENDED TO THE FORM 400B FOR
 SUBMITTAL.THIS WILL BE COMPARED TO THE
 ACTUAL SYSTEMS PROPOSED, AT A LATER, FOR
 INSTALLATION BY THE TENANT(S).THE
 ASSUMPTIONS LISTED ON THE APPENDIX SHEET
 SHALL BE AT LEAST THE MINIMUM STANDARD
 (LIGHTING, HVAC ETC) TO ALLOW THE WHOLE
 BUILDING TO BE OCCUPIED FOR IT'S
 INTENDED PURPOSE.
  
 6) FBC 13-103.1.2THE SUBMITTED ENERGY
 CODE COMPLIANCE FORMS WERE NOT SIGNED
 BY EITHER THE BUILDING OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
 ALSO THE ARCHITECT'S REGISTRATION NUMBER
 WAS NOT ENTERED ON SHEET TWO.ADDRESS
 THESE ITEMS TOGETHER WITH COMMENT 5.
  
 7) FBC 1403.3MASONRY VENEER.ANNOTATE
 THE PLANS GIVE THE SPECIFICATION FOR
 ATTACHMENT OF THE MASONRY VENEER.
  
 8) FBC 2309.7ATTIC VENTILATION.
 SHEET A-5.0, SECTION 1.ATTIC SPACE
 SHALL BE VENTILATED. AMEND THE "UNVENTED
 ATTIC" ANNOTATION ON SECTION 1.
  
 9) SHEET S-2.2, DETAIL 10, TYPICAL WALL
 SECTION AT ROOF EAVES.THE STATED
 1515 LB UPLIFT CAPACITY OF THE HETAL 16
 TRUSS ANCHOR EXCEEDS THE UPLIFT GIVEN IN
 THE 2003 SIMPSON CATALOGUE FOR 1-PLY
 TRUSS APPLICATION.AMEND THE DETAIL.
  
 10) SHEET S-2.2, DETAIL 12, GIRDER TRUSS
 CONNECTION TO STEEL BEAM.THE STATED
 2310 LB UPLIFT CAPACITY OF THE LTTI31
 TENSION TIE EXCEEDS THE UPLIFT GIVEN IN
 THE 2003 SIMPSON CATALOGUE.AMEND THE
 DETAIL.
  
 11) FBC 704.3SHEET S-2.2, DETAILS 4, 6
 AND 7.SUBMIT JUSTIFICATION (UL LISTING
 OR EQUIVALENT) FOR THE PROPOSED USE OF
 2X8 FIRE TREATED PLATE IN THE TENANT
 FIRE SEPARATION WALL OR AMEND THE DETAIL
  
 12) FBC 1606.1.7WIND LOAD.THE PLANS
 SHALL STATE EXTERIOR COMPONENT AND
 CLADDING DESIGN WIND PRESSURES FOR THE
 DOORS AND WINDOWS AND FOR THE ROOF.
  
 13) FBC* 2306.1ROOF SHEATHING NAIL
 SPACING.AMEND THE PLANS TO SPECIFY
 THE FASTENER TYPE AND SPACING.
  
 14) SUBMIT PRODUCT APPROVALS FOR THE
 WINDOWS, EXTERIOR DOORS AND ROOF.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
  
 15) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS