| Plan Review Notes For Permit 03111103 |
| Permit Number |
03111103 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-13 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLA. ADMIN. CODE | | | FLA. STATUTES | | | | | | 1) SHT P0.1 WATER ISOMETRIC, WATER HAM- | | | MER ARRESTOR SHALL BE LOCATED NEAR THE | | | FIXTURE IN AN "EFFECTIVE RANGE" NOT IN | | | THE CEILING AS SHOWN. PDI-WH 201 AND | | | MANUF. INSTALL. INSTRUC. (SEE NOTE #13) | | | 2) ENGINEERS SIGNATURE REQUIRED ON SEAL. | | | 61G15-23.002(1) & FS 471.025 PER FBPE & | | | BLDG OFFICIAL. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|