Plan Review Notes
Plan Review Notes For Permit 03111103
Permit Number 03111103
Review Stop M
Sequence Number 1
Notes
Date Text
2003-12-15 00:00:00DENIED:
 EQUIPMENT ROOM #126 AND THE ALCOVE NEAR
 CORRIDOR #147 ARE INDICATED AS A NEW
 FIRE RATED PARTITION.PLANS DO NOT
 INDICATE FIRE DAMPERS ON THE MECHANICAL
 PLANS.
  
 2001 FBC(M) 607.6, SPECIFIC LOCATIONS
 AND INSTALLATION DETAILS SHALL BE
 SHOWN AND IDENTIFIED ON THE BUILDING
 PLANS.PLEASE PROVIDE A NOTE SHOULD
 ANY OF THE PENETRATIONS COMPLY WITH
 THE EXCEPTIONS UNDER 607.1.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.