| 2003-12-15 00:00:00 | DENIED: | | | EQUIPMENT ROOM #126 AND THE ALCOVE NEAR | | | CORRIDOR #147 ARE INDICATED AS A NEW | | | FIRE RATED PARTITION.PLANS DO NOT | | | INDICATE FIRE DAMPERS ON THE MECHANICAL | | | PLANS. | | | | | | 2001 FBC(M) 607.6, SPECIFIC LOCATIONS | | | AND INSTALLATION DETAILS SHALL BE | | | SHOWN AND IDENTIFIED ON THE BUILDING | | | PLANS.PLEASE PROVIDE A NOTE SHOULD | | | ANY OF THE PENETRATIONS COMPLY WITH | | | THE EXCEPTIONS UNDER 607.1.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|