| Plan Review Notes For Permit 03111103 |
| Permit Number |
03111103 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-08 00:00:00 | 1) FIRE ALARM NOTES # 17 IS INCORRECT. | | | FIRE ALARM CIRCUITS SHALL BE CLASS A, | | | STYLE D, NOT CLASS B, STYLE C. | | | | | | 2) ANY CHANGES TO FIRE SPRINKLER | | | SYSTEM. SEPARATE PLANS AND PERMITS. | | | | | | 3) DOORS IN RECEPTION SWING IN. WHY | | | DONT THEY SWING OUT DUE TO OCCUPANT | | | LOAD. | | | | | | 4) DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|