Plan Review Notes
Plan Review Notes For Permit 03111103
Permit Number 03111103
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-12-08 00:00:001) FIRE ALARM NOTES # 17 IS INCORRECT.
 FIRE ALARM CIRCUITS SHALL BE CLASS A,
 STYLE D, NOT CLASS B, STYLE C.
  
 2) ANY CHANGES TO FIRE SPRINKLER
 SYSTEM. SEPARATE PLANS AND PERMITS.
  
 3) DOORS IN RECEPTION SWING IN. WHY
 DONT THEY SWING OUT DUE TO OCCUPANT
 LOAD.
  
 4) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910