| 2005-08-10 00:00:00 | ****** REVISION UNSAT ********* |
| | |
| | |
| | 1)NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | PLEASE NOTICE THERE ARE MORE THAN 75 |
| | RECESSED LT FIXTURES. |
| | |
| | 2)NOTE: PLEASE CORRELATE ALL CIRCUITING |
| | ON PLANS WITH THE REVISED SUBMITTED |
| | PANEL SCHEDULE. |
| | PLEASE SEE DINING RM CIRCUIT NOT ON |
| | PLANS? ETC. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE 210.52B1, WHICH |
| | REQUIRES DINING RM TO BE ON THE ONE OR |
| | MORE 20, #12, SMALL APPLIANCE CIRCUITS. |
| | PLEASE SEE DINING RM CIRCUIT ON PANEL |
| | SCHEDULE IS SHOWN AS #14 AWG AND 15A? |
| | |
| | 4)NOTE: PLEASE SHOW ALL ROOM/AREA |
| | DESIGNATIONS TO PLANS. |
| | 215.5 |
| | |
| | 5)NOTE: PLEASE SEE 410.8 FOR MIN |
| | CLEARENCE REQUIRED FOR RECESSED LTS IN |
| | CLOSETS. PLEASE SEE SOME APPEAR TO BE |
| | LOCATED TOO CLOSE TO POSSIBLE SHLEVING |
| | AREAS. THIS IS ONLY A NOTE AS NO |
| | SHELVING IS SHOWN. PLEASE SEE A MIN OF |
| | 18" IS TO BE PROVIDED FOR SHELVING AND |
| | THEN MIN CLEARENCE IS REQUIRED AFTER THE |
| | 18". PLEASE VERIFY THESE MIN AREAS. |
| | |
| | 6)NOTE: PLEASE SEE MISSING GFI RECEPT |
| | ALONG KITCHEN COUNTERSPACE. 210.52C1 |
| | |
| | 7)NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52, WITH IN 6' OF DOOR WAY? DINING |
| | AREA? BEDRM? |
| | |
| | 8)NOTE: PLEASE SEE GEN LT/RECEPT CIRCUIT |
| | SHOWN WITH A #10 EQUIPMENT GROUNDING |
| | CONDUCTOR?? MISPRINT? |
| | 250.122 |
| | |
| | |
| | PLEASE SEE MANY OF THE ABOVE ITEMS HAVE |
| | BEEN REDLINEDS ON PLANS AT LOCATION SOF |
| | THE ABOVE COMMENTS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL THIS |
| | OFFICE. |
| | |