| 2004-06-10 00:00:00 | ************ UNSAT 4TH TIME *********** |
| | |
| | PLEASE SEE NOTES FROM PREVIOUS REVIEWS. |
| | PLEASE SEE ONLY TWO OF THE PREVIOUS |
| | 6 NOTES WERE ADDRESSED. |
| | |
| | 1)NOTE: |
| | NOTE #1OK. TURQUOISE ENG NAME WAS |
| | REMOVED. |
| | |
| | 2)NOTE: |
| | NOTE #2 NO. PLEASE SHOW "ALL" CIRCUITING |
| | ON PLANS AND CORRELATE WITH THE SUBMITT- |
| | -ED PANEL SCHEDULE. PLEASE SEE 2002 NEC |
| | FOR ALL MIN CIRCUITS REQUIRED IN A |
| | DWELLING UNIT. WASHER? DRYER? 215.5, |
| | 220.16,220.18, |
| | |
| | 3)NOTE: |
| | NOTE #3OK |
| | |
| | 4)NOTE: |
| | NOTE #4NO, SOME RECEPTS STILL MISSING |
| | FOR 2' OF WALL SPACE. |
| | |
| | 5)NOTE: |
| | NOTE #5 NO, PLEASE LIST THE REQUIRED |
| | ARC FAULT PROTECTED CIRCUITS PER 2002 |
| | NEC 210.12 |
| | PLEASE SEE 2002 NEC REQUIRES THIS FOR |
| | LTS/SD'S RECEPTS/FANS ETC. ALL "OUTLETS" |
| | IN SLEEPING RMS. |
| | |
| | 6)NOTE: |
| | NOTE #6NO, PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | PLEASE SEE ONE OF THESE SETS ARE NOW |
| | BEING RETAINED ALSO DUE TO REPEAT |
| | COMMENTS. |
| | PLEASE ALSO SEE ATTACHED COPY OFTHE |
| | FS 553.80(2)(B). IF ANY OF THE COMMENTS |
| | FOR CODE COMPLIANCE ARE NOT ADDRESSED |
| | ON NEXT REVIEW A 4X FEE WILL BE ACCESSED |
| | TO THE DESIGN PROFESSIONAL. |
| | ****PLEASE SEE ATTACHED COPY***** |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | ONCE AGAIN, PLEASE DO NOT HESITATE TO |
| | CALL. AS OF THIS REVIEW, DESIGNER OF |
| | RECORD HAS NOT CONTACTED ELECTRICAL |
| | PLAN REVIEW STAFF FOR ANY QUESTIONS. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |