| 2004-05-08 00:00:00 | ******** UNSAT ********** |
| | |
| | PLEASE SEE NOTES FROM FIRST TWO |
| | REVIEWS HAVE STILL NOT BEEN ADDRESSED. |
| | PLEASE SEE THE FOLLOWING. |
| | |
| | 1)NOTE: PLANS MUST CONTAIN ALL LICENSE |
| | #'S ON TITLE BLOCK AS REQ'D UNDER FAC |
| | 61G15-23.002. PLEASE SEE FS 471.023 |
| | TURQUOIUSE INC. MUST HAVE A CA#. |
| | THERE IS NO CA# FOUND WITH DBPR/ FBPE'S |
| | THIS COMMENT HAS BEEN MADE ON PREVIOUS |
| | REVIEWS ON THIS PROJECT AND OTHER |
| | PROJECTS SUBMITTED TO THE CITY OF WPB |
| | FOR PERMIT. |
| | PLEASE ALSO SEE FS 471.025, DATE MUST |
| | ALSO BE SIGNED ON PLANS WHEN ENGINEER |
| | SIGNS HIS/HER SIGNATURE. |
| | WE ARE NOW RETAINING ONE SET OF PLANS |
| | TO BE TURNED OVER TO FBPE'S FOR REVIEW |
| | FOR ABOVE MENTIONED. |
| | |
| | 2)NOTE: PLANS MUST SHOW ALL MIN CIRCUIT- |
| | -ING AS SET FORTH PER 2002 NEC. |
| | PLEASE SHOW CIRCUITS ON PLANS AND |
| | CORRELATE WITH THE SUBMITTED PANEL |
| | SCHEDULE. |
| | |
| | 3) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 4)NOTE: PLEASE SHOW OUTLET SPACING PER |
| | 210.52. 2',6`,12` RULE. MISSING SOME. |
| | |
| | 4 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 5 )NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |