| Plan Review Notes For Permit 03111058 |
| Permit Number |
03111058 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-02-19 00:00:00 | DENIED: | | | SEE COMMENT #1 BY ROBERT BROWN.PLEASE | | | RESUBMIT PLANS FOR APPROVAL.PLANS | | | ARE OTHERWISE CODE COMPLIANT. | | | | | | PROVISO: | | | 1.HVAC NOTE #8, FAN SHUTDOWN BY DUCT | | | SMOKE DETECTOR SHALL HAVE NOTIFICATION | | | TO ALARM/STROBE IN NORMALLY OCCUPIED | | | AREAS PER NFPA 90A 4-4.4.3. | | | | | | 2.CONDENSATE FROM THE RTU SHALL | | | TERMINATE TO STORM DRAIN OR AN APPROVED | | | DRY WELL. |
|