| Plan Review Notes For Permit 03111058 |
| Permit Number |
03111058 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-04 00:00:00 | *************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE THAT PER FS AND FAC | | | 481.221 AND 61G1-16.004. SIGNED AND | | | SEALED PLANS MUST CONTAIN A VISABLE | | | SIGNATRE THAT CONTAINS A MIN OF FIRST | | | AND LAST NAME. PLEASE ALSO SEE MISSING | | | INFORMATION REQUIRED ON TITLE BLOCK FOR | | | ARCH/FIRM OF RECORD. | | | | | | 2)NOTE: PLANS REFERENCE2001 NEC. | | | PLEASE SEE THAT THEREIS NO 2001 AND | | | WE ARE CURRENTKY UNDER THE 2002 NEC. | | | | | | PLEASE SUBMITTHE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVEIW | | | 561-805-6717 | | | [email protected] |
|