| 2004-01-21 00:00:00 | *****CORRECTIONS****** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)SEE PREVIOUS LIST, ITEM #1.NOT |
| | ADDRESSED.SUBMIT A COPY OF A SURVEY |
| | FOR THIS PROPERTY, ADDRESSING TABLE 600 |
| | ISSUES.SHOW THE DISTANCE BETWEEN THE |
| | TWO BUILDINGS ON THIS PROPERTY, DISTANCE |
| | TO THE PROPERTY LINE.SHOW THE |
| | ASSUMED PROPERTY LINE, WITH DIMENSIONS, |
| | AND SUBMIT CALCULATIONS SHOWING TABLE |
| | 600 COMPLIANCE.FAILURE TO PROVIDE THE |
| | REQUESTED INFORMATION MAY RESULT IN |
| | ADDITIONAL PERMITTING DELAYS. |
| | |
| | 2.)SEE PREVIOUS LIST, ITEM #3, NOT |
| | ADDRESSED. |
| | |
| | 3.)THE PLANS MAKE REFERENCE "TO CODE". |
| | THIS IS NOT AN ACCEPTABLE AS A DETAIL, |
| | FBC104.2.1.ALL MATERIALS, DIMENSIONS, |
| | ETC. MUST BE SPECIFIED. |
| | |
| | 4.)SEE PREVIOUS LIST, ITEM #5, |
| | REGARDING FBC3401.7.2.6.SOME COMMENTS |
| | ARE RELATED TO THIS CODE SECTION |
| | (ALTERATIONS OVER 50%). |
| | |
| | 5.)THE STAIRS DO NOT COMPLY WITH FBC |
| | 1007.3. |
| | |
| | 6.)SEE PREVIOUS LIST, ITEM #9.CANNOT |
| | SPECIFY "TO CODE".ALL GUARDRAIL AND |
| | HANDRAILS DETAILS ARE TO COMPLY WITH |
| | FBC1608, FBC1007.5, FBC1015.THE |
| | DETAILS SHOWN ARE NOT CODE COMPLIANT IN |
| | DESIGN, INCLUDING HEIGHT, MAKE NO |
| | REFERENCE TO STRUCTURAL DESIGN LOAD. |
| | THIS ALSO APPLIES TO PREVIOUS LIST #10, |
| | EITHER NOT ADDRESSED OR ADDRESSED IN A |
| | MANNER WHICH IS NOT CODE COMPLIANT. |
| | |
| | 7.)CHANGES MADE TO THE PLAN IN INK |
| | ARE TO BE INITIALED BY THE ARCHITECT. |
| | |
| | 8.)SEE PREVIOUS LIST, ITEM #35. MANY |
| | CHANGES WERE DONE TO THE PLAN AND NOT |
| | INDICATED IN ANY MANNER. |
| | |
| | 9.)ADDITIONAL FEES DUE, $2163.60, |
| | BZ235307.PLEASE RETURN THE BZ GIVEN |
| | AT THE LAST REVIEW. |
| | |
| | 10.)SEE PREVIOUS LIST, ITEM #12.NOT |
| | ADDRESSED.TO MY KNOWLEDGE THE PRODUCT |
| | APPROVALS SUBMITTED FOR DOORS AND |
| | WINDOWS DO NOT HAVE ANY FIRE RATING. |
| | |
| | 11.)SEE PREVIOUS LIST, ITEM #13, |
| | INDICATE CONSTRUCTION TYPE ON THE PLAN. |
| | |
| | 12.)SHEET 4, LSAT 2", MUST SPECIFY A |
| | MODEL #, NOT A DIMENSION.LSTA IS A |
| | WOOD-TO-WOOD CONNECTOR WHICH YOU ARE |
| | USING IN A WOOD-TO-MASONRY APPLICATION. |
| | EITHER SUBMIT DOCUMENTATION FROM THE |
| | MANUFACTURER SHOWING THAT THIS |
| | APPLICATION IS ACCEPTABLE, SPECIFY A |
| | DIFFERENT CONNECTOR, OR SUBMIT SEALED |
| | CALCULATIONS FOR THIS CONNECTOR IN THIS |
| | APPLICATION.CHECK ALL CONNECTORS. |
| | |
| | 13.)THE WINDOW/DOOR BUCK DETAIL |
| | SPECIFIES "CASE HARDENEND NAILS",SPECIFY |
| | SIZE.THE FASTENERS FOR THE WINDOW |
| | CONFLICT WITH THE PRODUCT APPROVAL IN |
| | BOTH DIAMETER AND SPACING, SEE ATTACHED |
| | HIGHLIGHTED PRODUCT APPROVAL. |
| | |
| | 14.)NOTE THAT THE TEMPERED WINDOWS |
| | SHOWN ON THE 2ND FLOOR ARE ALSO REQUIRED |
| | TO HAVE A FIRE RESISTANCE RATING, FBC |
| | 1006.2.4.DOCUMENTATION SUBMITTED FOR |
| | THIS WINDOW IS TO SHOW COMPLIANCE WITH |
| | CHAPTER 16, FBC2405.2, AND FBC1006.2.4. |
| | |
| | 15.)THE GUARDRAIL IS TO BE A MINIMUM |
| | OF 44", FBC1015.2.THE DETAILS SHOW |
| | THE STAIRRAIL (WHICH SERVES AS A |
| | GUARDRAIL) AT 30" AND 36". |
| | |
| | 16.)HANDRAIL REQUIRED FOR STAIR ON |
| | BOTH SIDES, FBC1007.5. |
| | |
| | 17.)SEE PREVIOUS LIST, ITEM #22, |
| | NOT ADDRESSED. |
| | |
| | 18.)SEE PREVIOUS LIST, ITEM #24. |
| | ENERGY CALCS REQUIRED. |
| | |
| | 19.)SEE PREVIOUS LIST, ITEM #25. |
| | RATHER THAN ADDRESS THE COMMENT THE |
| | INSULATION WAS REMOVED.INSULATION IS |
| | REQUIRED FOR THE FLOOR (OCCUPANCY |
| | SEPARATION) AND ROOF. |
| | |
| | 20.)SEE PREVIOUS LIST, ITEM #29.NOT |
| | ADDRESSED.IF THE REQUIRED INFORMATION |
| | IS NOT SUBMITTED PRIOR TO PERMIT |
| | ISSUANCE, A SEPARATE PERMIT FOR SHUTTERS |
| | WILL BE REQUIRED. |
| | |
| | 21.)SEE PREVIOUS LIST, ITEM #26.ALSO |
| | HAVE THE NEW PLANS APPROVED BY HISTORIC |
| | PRIOR TO RESUBMITTAL. |
| | |
| | 22.)SPECIFY THE SPACING AND LENGTH OF |
| | THE ANCHOR BOLT, SHEET 4, WALL SECTION |
| | AT BALCONY. |
| | |
| | 23.)SEPARATE PERMITS REQUIRED. |
| | |
| | 24.)SEE PREVIOUS LIST, ITEM #37.NOT |
| | ADDRESSED. |
| | |
| | 25.)RESOLVE ANY EXPIRED PERMIT ISSUES |
| | PRIOR TO ISSUANCE OF THIS PERMIT. |
| | |
| | 26.)AS DISCUSSED SEVERAL TIMES WITH |
| | THE CONTRACTOR, IF YOU WISH TO OBTAIN A |
| | PERMIT FOR THE ROOF JOISTS, SHEATHING, |
| | AND ROOF COVERING ONLY, SUBMIT A PERMIT |
| | APPLICATION WITH PLANS SHOWING ONLY |
| | THESE ITEMS.PLANS ARE REQUIRED SHOWING |
| | DRAINAGE, DESIGN LOAD AND UPLIFT. |
| | |
| | 27.)SLIDING GLASS DOOR PRODUCT |
| | APPROVALS WERE SUBMITTED, NONE SHOWN ON |
| | THE PLAN. |
| | |
| | 28.)MULLION PRODUCT APPROVALS |
| | REQUIRED, SUBMIT 2 COPIES. |
| | |
| | 29.)SHEET 2 IS NOW MISSING FROM THE |
| | OLD SETS OF PLANS.ALWAYS SUBMIT ALL |
| | OLD SHEETS WITH RESUBMITTAL.THE NEW |
| | SHEET 2 NOW SHOWS WINDOWS AS EXISTING. |
| | MY UNDERSTANDING IS THAT THIS BUILDING |
| | DOES NOT HAVE WINDOWS AND THAT THIS WORK |
| | IS TO BE INCLUDED IN THIS PERMIT. |
| | REVISE. |
| | |
| | 30.)SEE ATTACHED NOTICE IN REGARDS TO |
| | FS553.80(2)(B). |
| | |
| | 31.)PAY FEES PRIOR TO RESUBMITTAL. |
| | |
| | 32.)TWO COPIES OF ALL DOCUMENTATION |
| | REQUIRED FOR PERMITTING, ONLY ONE SET |
| | OF PLANS WERE SUBMITTED. |
| | |
| | 33.)SEE PREVIOUS LIST, ITEM #6.THE |
| | FIRST FLOOR SHOULD BE DECLARED AS |
| | MERCANTILE, 2ND FLOOR AS R2 FBC CH.3. |
| | |
| | 34.)SEE PREVIOUS LIST, ITEM #37.IN |
| | ADDITION TO PROVIDING THE REQUESTED |
| | INFORMATION FOR THE OCCUPANCY SEPARATION |
| | ALSO PROVIDE SAME FOR TENANT SEPARATION |
| | ON THE 1ST FLOOR, FBC704.3.1. |
| | |
| | 35.)"EXISTING PLUMBING PIPE" IS SHOWN |
| | ON THE PLAN (SHEET2, 2ND FLOOR). |
| | PENETRATIONS ARE TO COMPLY WITH FBC705.2 |
| | .1.3, 705.4. |