| Plan Review Notes For Permit 03111034 |
| Permit Number |
03111034 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLA. ADMIN. CODE | | | FLA. STATUTES | | | | | | 1) SUBMIT CALCULATIONS FOR PRIMARY AND | | | SECONDARY ROOF DRAINS PER SECTIONS 1106, | | | AND 1107 AND ALL SUBSECTIONS. SHOW LOC- | | | ATION OF ALL PRIMARY ROOF DRAINS AND | | | THE LOCATION OF SECONDARY OR OVERFLOW | | | SCUPPER DRAINS. SUBMIT A DETAIL OF | | | SCUPPERS. IF GUTTER AND DOWNSPOUTS, SHOW | | | THE SIZE OF THE GUTTERS PER TABLE 1106.6 | | | AND INDICATE SIZE OF DOWNSPOUTS. DOWN- | | | SPOUTS SHALL TERMINATE MIN. OF 1' OFF | | | SIDE OF STRUCTURE WALL. | | | 2) THE PERSONAL SEAL, SIGNATURE AND DATE | | | OF THE ARCHITECT SHALL APPEAR ON ALL | | | DOCUMENTS TO BE FILED FOR PUBLIC RECORD, | | | ***THE DATE IS MISSING.*** 61G1-16.003 | | | FS 481.2055 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|