| Plan Review Notes For Permit 03111034 |
| Permit Number |
03111034 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-11 00:00:00 | 1) BUILDING ADDRESS REQUIRED ON PROPER | | | ELEVATION. A MINIMUM OF 6" HIGH | | | NUMBERS ARE REQUIRED. | | | | | | 2) PLANS INDICATE REHAB OF SHELL ONLY | | | FOR OFFICE BUILDING. | | | | | | 3) PLEASE PROVIDE MORE DETAILS ON ALL | | | EXISTING HANDRAILS AND GUARDRAILS. | | | | | | 4) PLANS DO NOT INDICATE PROPOSED | | | OCCUPANT LOAD FOR THE BUILDING. | | | | | | 5) PLEASE PROVIDE PRESCRIPTIVE STRENGTH | | | REQUIREMENTS FOR HANDRAILS AND | | | GUARDRAILS. | | | | | | 6) PLEASE EXPLAIN SINGLE EXIT RATIONALE | | | FROM SECOND FLOOR. WHAT EXCEPTION | | | TO THE CODE ARE YOU USING THAT ALLOWS | | | THIS. | | | | | | 7) PLEASE PROVIDE MORE DETAILS ON | | | EXISTING STAIR. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|