2004-04-24 00:00:00PROVISO:
 PER 2001 FBC(M) 607.4, DUCTS EXTENDING
 THROUGH MORE THAN ONE FLOOR SHALL BE
 ENCLOSED IN A FIRE RATED SHAFT.DUCTS
 THAT PENETRATE ONLY ONE FLOOR SHALL BE
 PROTECTED WITH A FIRE DAMPER AT THE
 FLOOR PENETRATION.
  