| Plan Review Notes For Permit 03111029 |
| Permit Number |
03111029 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-12 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLA. ADMIN. CODE | | | FLA. STATUTES | | | | | | 1) SHT A-2.0 SHOW ACCESSIBLE W/C TO BE | | | 18" OFF WALL TO CENTER OF FIXTURE. | | | CHAPTER 11 FIGURE 28. | | | 2) SHT A-2.0 SHOW DETAILS & MEASURMENTS | | | FOR FOL. 11-4.16.3 W/C HEIGHT, 11-4.22 | | | .3 CLEAR FLOOR SPACE, CLEARANCE 11-4.19. | | | 2, EXPOSED PIPES AND SURFACES 11-4.19.4, | | | DRINKING FOUNTAIN SPOUT HEIGHT 11-4.15.2 | | | TURNING SPACE 11-4.23.3. | | | 3) SHT P-1, GENERAL SPECIFICATIONS: #22 | | | AIR CHAMBERS ARE NOT APPROVED. DELETE | | | REFERENCE. | | | 4) SHT P-2 DOMESTIC WATER RISER, WATER | | | HAMMER ARRESTORS, WHEN USED SHALL BE | | | LOCATED NEAR THE FIXTURE IN AN "EFFECT- | | | IVE RANGE" NOT IN THE CEILING AS SHOWN. | | | PDI-WH 201 AND MANUF. INSTALL. INSTRUCT- | | | IONS. | | | 5) IF PRACTICING THROUGH A DULY AUTHOR- | | | IZED ENGINEERING BUSINESS, ENGINEERS | | | SHALL LEGIBLY INDICATE THEIR NAME AND | | | LICENSE NUMBER, AS WELL AS, THE NAME, | | | ADDRESS AND CERTIFICATE OF AUTHORIZATION | | | ON THE ENGINEERING BUSINESS ON EACH | | | SHEET. 61G15-23.002(2) & FS 471.025. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|