| Plan Review Notes For Permit 03111029 |
| Permit Number |
03111029 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-05 00:00:00 | DENIED: | | | 1.PLANS SHEET M2.1 KEYNOTES #6 SHOULD | | | THIS READ 1 & #3 IS INIDICATED AS 7. | | | PLEASE CORRELATE. | | | | | | 2.KEYNOTE 6 INDICATES FIRE DAMPERS | | | AT THE 3RD AND 1ST FLOORS.PLEASE | | | CLARIFY IF THIS DUCT IS IN A SHAFT AND | | | THE LOCATION OF THE FIRE DAMPERS ARE | | | AT THE PENETRATION INTO THE SHAFT OR | | | AT THE FLOOR.PLEASE NOTE PER 2001 | | | FBC(M) 607.4 & NFPA 90A 3-3.4.1. | | | | | | 3.NEW EQUIPMENT STANDS INDICATED ON | | | PLAN SHEET A-1.3 SHALL COMPLY WITH | | | 2001 FBC 1511.7. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|