2003-12-05 00:00:00DENIED:
 1.PLANS SHEET M2.1 KEYNOTES #6 SHOULD
 THIS READ 1 & #3 IS INIDICATED AS 7.
 PLEASE CORRELATE.
  
 2.KEYNOTE 6 INDICATES FIRE DAMPERS
 AT THE 3RD AND 1ST FLOORS.PLEASE
 CLARIFY IF THIS DUCT IS IN A SHAFT AND
 THE LOCATION OF THE FIRE DAMPERS ARE
 AT THE PENETRATION INTO THE SHAFT OR
 AT THE FLOOR.PLEASE NOTE PER 2001
 FBC(M) 607.4 & NFPA 90A 3-3.4.1.
  
 3.NEW EQUIPMENT STANDS INDICATED ON
 PLAN SHEET A-1.3 SHALL COMPLY WITH
 2001 FBC 1511.7.
  