| Plan Review Notes For Permit 03111029 |
| Permit Number |
03111029 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-08 00:00:00 | 1) COULD NOT LOCATE ANY EMERGENCY LIGHTS | | | ON SECOND FLOOR ELECTRICAL PLAN. | | | | | | 2) COULD NOT LOCATE ELECTRICAL PLANS | | | FOR THE FIRST FLOOR. | | | | | | 3) PLEASE EXPLAIN WHY DOOR SWINGS OUT | | | ON STAIR SHOWN ON PAGE A-1.2. | | | | | | 4) PLEASE PROVIDE MORE DETAILS ON LIVE | | | WORK LOFT. | | | | | | 5) WHY DOES THE STAIR DOOR ON THE 4TH | | | FLOOR SWING OUT. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|