2003-12-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03111029
 ADD: 219/ 221 CLEMATIS ST
 CONT: L. DAVIS CONSTRUCTION
 TEL: (561)718-8161
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 ACTION: DENIED
  
 1) SHEET A-1.0/ A-1.1 REMOVE REFRENCES
 OF THE SBC (STANDARD BUILDING CODE) AND
 INSERT THE 2001 FLORIDA BUILDING CODE
 2002 REVISIONS.
  
 2) BACK STAIRWELL, THE DOOR SWINGS INTO
 THE CLEAR FLOOR SPACE OF THE STAIRWELL?
  
 3) SHEET A-1.0 NOTE# 4, INDICATES NEW
 A/C WORK WITHIN THE STAIR VESTIBULE.
 1006.1.3.1 SEE APPROVED PENETRATIONS IN-
 TO STAIRWELL, PLANS ARE NOT CLEAR AS TO
 WHAT WORK THAT WILL BE ACCOMPLISHED.
  
 4) PLANS INDICATE THIS BUILDING IS FIRE
 SPRINKLERED, IS THIS FIRE SPRINKLER
 SYSTEM SUPERVISED? IF SO THEN A AREA OF
 RESCUE ASSISTANCE IS NOT REQUIRED.
  
 5) DETAIL SHEET A-2.0, THE PLANS INDI-
 CATE DIRECTLY BEHIND THE W. C. A GRAB
 BAR 3'-0" OVERALL DIMENSION FROM THE
 CORNER. SEE 11-4.17.6 THE DETAIL SHEETS
 INDICATE A MAXIMUM OF 6" FROM THE CORNER
 THEN A 36" BAR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026