| Date |
Text |
| 2004-05-03 00:00:00 | **********UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE NOTE FOR ARC FAULT |
| | PROTECTION IS FROM THE 99 NEC. |
| | PLEASE SEE 210.12 2002 NEC FOR CORRECT- |
| | -ION OF NOTE. PLEASE ALSO SEE NOTE |
| | PERTAINING TO SD'D BEING WIRED FROM |
| | KIT/BATH LTS. IS THIS IS DONE AFCI WILL |
| | BE REQ'D ON THOSE ITEMS ALSO. |
| | |
| | 2)NOTE: PLEASE CORRELATE ADDRESS ON PLAN |
| | -S/ APPLICATION W/ WHAT SHOWS AS PARCEL |
| | FILE. ONE SHOWS 219,221, 225, ETC. |
| | PLEASE SEE BLDG REVIEW COMMENTS FOR |
| | |
| | 3)NOTE: PLEASE PROVIDE COPY OF ENGINEERS |
| | SIGNATURE FROM LICENSE/DRIVERS LICENSE. |
| | THESE WILL BE HELD IN FILE FOR ANY |
| | FUTURE REFERENCE. |
| | ANY PERSONEL INFORMATION MAY BE CROSSED |
| | OUT/ADDRESS ETC. |
| | FS 471.025, COMPLETE SIGNATURE IS REQ'D |
| | PLEASE CALL FOR ANY QUESTIONS. |
| | |
| | 4)NOTE: PLEASE SEE LOADS FOR A/C UNITS |
| | ARE SHOWN AS XXX. ?? PLEASE SHOW AND |
| | CORRELATE WITH A/C MECH PLANS. MECH PLAN |
| | -S SHOW 5.3 KW?? |
| | |
| | 5)NOTE: PLEASE CLARIFY METHOD OF CONTROL |
| | FOR LTS TO ROOF AREA FROM BOTH LEVELS? |
| | 210.70/ LS 101 5-8 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |