Plan Review Notes
Plan Review Notes For Permit 03111027
Permit Number 03111027
Review Stop E
Sequence Number 2
Notes
Date Text
2004-05-03 00:00:00**********UNSAT **************
  
 1)NOTE: PLEASE SEE NOTE FOR ARC FAULT
 PROTECTION IS FROM THE 99 NEC.
 PLEASE SEE 210.12 2002 NEC FOR CORRECT-
 -ION OF NOTE. PLEASE ALSO SEE NOTE
 PERTAINING TO SD'D BEING WIRED FROM
 KIT/BATH LTS. IS THIS IS DONE AFCI WILL
 BE REQ'D ON THOSE ITEMS ALSO.
  
 2)NOTE: PLEASE CORRELATE ADDRESS ON PLAN
 -S/ APPLICATION W/ WHAT SHOWS AS PARCEL
 FILE. ONE SHOWS 219,221, 225, ETC.
 PLEASE SEE BLDG REVIEW COMMENTS FOR
  
 3)NOTE: PLEASE PROVIDE COPY OF ENGINEERS
 SIGNATURE FROM LICENSE/DRIVERS LICENSE.
 THESE WILL BE HELD IN FILE FOR ANY
 FUTURE REFERENCE.
 ANY PERSONEL INFORMATION MAY BE CROSSED
 OUT/ADDRESS ETC.
 FS 471.025, COMPLETE SIGNATURE IS REQ'D
 PLEASE CALL FOR ANY QUESTIONS.
  
 4)NOTE: PLEASE SEE LOADS FOR A/C UNITS
 ARE SHOWN AS XXX. ?? PLEASE SHOW AND
 CORRELATE WITH A/C MECH PLANS. MECH PLAN
 -S SHOW 5.3 KW??
  
 5)NOTE: PLEASE CLARIFY METHOD OF CONTROL
 FOR LTS TO ROOF AREA FROM BOTH LEVELS?
 210.70/ LS 101 5-8
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]