| Plan Review Notes For Permit 03111027 |
| Permit Number |
03111027 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-11 00:00:00 | 1) NO EMERGENCY LIGHTING SHOWN IN | | | STAIRWAY. | | | | | | 2) STAIR SECTION INDICATES 9 TREADS | | | @ 9.47". STAIR TREADS SHALL BE AT | | | LEAST 11". RISERS ARE AT 7 5/8". RISERS | | | SHALL NOT EXCEED 7". | | | | | | 3) PLEASE PROVIDE PRESCRIPTIVE | | | REQUIREMENTS FOR HANDRAILS AND | | | GUARDRAILS. | | | | | | 4) PLANS INDICATE FIRE SPRINKLER | | | PROTECTION, HOWEVER NO FIRE SPRINKLER | | | PLANS ARE PROVIDED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|