Plan Review Notes
Plan Review Notes For Permit 03111027
Permit Number 03111027
Review Stop B
Sequence Number 1
Notes
Date Text
2003-12-23 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) FBC 1004.1.5EGRESS FROM OBSERVATION
 DECK.THE TRAVEL DISTANCE FROM THE MOST
 REMOTE POINT ON THE OBSERVATION DECK TO
 DOOR E1 IS APPROX. 70 FT.ANNOTATE THE
 PLANS TO STATE THAT THE EXISTING STAIR
 BEYOND DOOR E1 IS A PROTECTED 'EXIT'
 STAIR WITH 2-HOUR FIRE-RATED WALLS AND
 90-MINUTE RATED DOORS ALONG THE ENTIRE
 ROUTE TO EXIT DISCHARGE.
  
 3) FBC 1007.3.1 (EXCEPTION 1)STAIR
 TREADS AND RISERS.IT IS NOTED THAT THE
 THE NEW STAIR HAS 9.47" TREADS AND
 7.625" RISERS. ANNOTATE/DETAIL THE PLANS
 TO ENSURE THAT THE TREADS (LESS THAN
 10") HAVE AN EFFECTIVE PROJECTION OF
 APPROX. 1" OVER THE TREAD BELOW.NOTE
 THAT FIRE PLAN REVIEWER HAS ALSO
 COMMENTED ON THE STAIR.
  
 4) FBC 1603OBSERVATION DECK DEAD LOAD.
 SHEET A-4.0 SHOWS THE SAME DEAD LOAD
 (25 PSF) FOR BOTH THE 'ROOFTOP DECK
 LOAD' AND THE 'ROOF LOAD'.SHEET A-1.1,
 KEYED NOTE 2 SPECIFIES TWO DECKING
 OPTIONS FOR THE OBSERVATION DECK AREA,
 BUT THE ABOVE DEAD LOADS DO NOT SHOW ANY
 DIFFERENCE BETWEEN 'ROOF' AND 'ROOFTOP
 DECK' TO ACCOUNT FOR THE WORST CASE DECK
 SYSTEM LOAD.AMEND/ANNOTATE THE PLANS.
  
 5) FBC 1608.2.1THE HANDRAIL SHALL BE
 DESIGNED AND CONSTRUCTED FOR A
 CONCENTRATED LOAD OF 200 LB APPLIED AT
 ANY POINT, AND IN ANY DIRECTION, TO
 PRODUCE MAXIMUM STRESS IN EACH OF THE
 COMPONENTS OR SUPPORTS.AMEND/ANNOTATE
 THE PLANS.THE GUARDRAIL DESIGN
 CRITERIA STATED ON SHEET A-4.0 HAS
 ALREADY BEEN NOTED.
  
 6) 61G15-23.002(2)FL. ADMIN. CODE.
 PLANS SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE EITHER THE NAME,
 AND LICENSE NUMBER OF THE ENGINEER.
 UNDER THE ENGINEER'S SEAL ON THE
 MECHANICAL, ELECTRICAL AND PLUMBING
 SHEETS IN THE BOX PROVIDED FOR THE SEAL,
 THE NAME AND LICENSE NUMBER OF
 MICHAEL J. KRAVIT SHALL BE STRUCK OUT,
 AND THE NAME AND LICENSE NUMBER OF THE
 ENGINEER SEALING THE MECHANICAL AND
 PLUMBING SHEETS OR THE ELECTRICAL SHEETS
 SHALL BE PRINTED.
  
 7) FBC 13-103.1.1.1SHEET 2 OF THE
 SUBMITTED ENERGY CODE COMPLIANCE FORM
 SHALL INCLUDE THE NAME AND LICENSE #
 OF THE ARCHITECT, AND THE ENGINEERS
 RESPONSIBLE FOR THE DESIGN OF THE
 ELECTRICAL, LIGHTING, MECHANICAL AND
 PLUMBING SYSTEMS, TO CERTIFY COMPLIANCE.
  
 8) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]