| Plan Review Notes For Permit 03110949 |
| Permit Number |
03110949 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-06 00:00:00 | DENIED; | | | RISER DIAGRAM DOES NOT MATCH FLOOR PLAN. | | | W/M AND L.T. ARE NOT SIDE BY SIDE.BUILD- | | | ING DRAIN SHOULD RUN STRATE TO THE BACK | | | BATHROOM. BACK BATHROOM HAS SHR, NOT TUB | | | SIZE VENTS THRU ROOF. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|