| Plan Review Notes For Permit 03110934 |
| Permit Number |
03110934 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-08 00:00:00 | DENIED: | | | 1.RETURN AIR REQUIRED FROM BEDROOM AREAS | | | PER REVISED 2001 FBC(M) 601.4 EFFECTIVE | | | JUNE 30, 2003 - SIZING SHALL BE AS | | | FOLLOWS: | | | DUCTED RETURN SHALL BE EQUAL TO THE | | | SUPPLY. | | | | | | TRANSFER DUCTS SHALL BE 1 1/2 TIMES THE | | | SUPPLY AIR.MASTER BEDROOM SHALL | | | INCLUDE ALL SUPPLY AIR. | | | | | | TRANSFER GRIILES SHALL USE 50 SQ INCHES | | | PER 100 CFM OF SUPPLY AIR. | | | | | | 2.AUXILIARY DRAIN PAN REQUIRED PER 2001 | | | FBC(M) 307.2. | | | | | | PLEASE REVISE PLANS TO REFLECT CODE | | | COMPLIANCE. |
|