2003-12-08 00:00:00DENIED:
 1.RETURN AIR REQUIRED FROM BEDROOM AREAS
 PER REVISED 2001 FBC(M) 601.4 EFFECTIVE
 JUNE 30, 2003 - SIZING SHALL BE AS
 FOLLOWS:
 DUCTED RETURN SHALL BE EQUAL TO THE
 SUPPLY.
  
 TRANSFER DUCTS SHALL BE 1 1/2 TIMES THE
 SUPPLY AIR.MASTER BEDROOM SHALL
 INCLUDE ALL SUPPLY AIR.
  
 TRANSFER GRIILES SHALL USE 50 SQ INCHES
 PER 100 CFM OF SUPPLY AIR.
  
 2.AUXILIARY DRAIN PAN REQUIRED PER 2001
 FBC(M) 307.2.
  
 PLEASE REVISE PLANS TO REFLECT CODE
 COMPLIANCE.