| 2003-12-08 00:00:00 | 1) DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2) DOMESTIC COLD WATER PIPING CANNOT | | | RUN THRU EXISTING STAIR # 1. | | | | | | 3) ELECTRICAL NOTES # 13 CONCERNING | | | DUCT SMOKE DETECTORS IS INCORRECT. | | | DUCT SMOKE DETECTORS WHEN ACTIVATED | | | SHALL CAUSE THE FIRE ALARM SYSTEM | | | TO SOUND NOT SUPERVISORY SIGNAL. | | | | | | 4) SECURITY LOCKS, NOTE # 11 SHALL | | | COMPLY WITH SPECIAL LOCKING ARRANGEMENTS | | | PER CHAPTER 7 OF THE LIFE SAFETY CODE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|