Plan Review Notes
Plan Review Notes For Permit 03110910
Permit Number 03110910
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-12-08 00:00:001) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) DOMESTIC COLD WATER PIPING CANNOT
 RUN THRU EXISTING STAIR # 1.
  
 3) ELECTRICAL NOTES # 13 CONCERNING
 DUCT SMOKE DETECTORS IS INCORRECT.
 DUCT SMOKE DETECTORS WHEN ACTIVATED
 SHALL CAUSE THE FIRE ALARM SYSTEM
 TO SOUND NOT SUPERVISORY SIGNAL.
  
 4) SECURITY LOCKS, NOTE # 11 SHALL
 COMPLY WITH SPECIAL LOCKING ARRANGEMENTS
 PER CHAPTER 7 OF THE LIFE SAFETY CODE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910