| | PLEASE REVISE THE PLANS TO INDICATE THE |
| | FOLLOWING FOR CODE COMPLIANCE. |
| | |
| | 1} PLEASE NOTE THAT ALL PLANS |
| | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- |
| | ING A TITLE BLOCK, MUST BE SIGNED, |
| | DATED AND SEALED BY THE ARCH/ENGINEER |
| | OFRECORD. PER FS/FAC 481.221 & 471.025 |
| | |
| | 2} PLEASE SEE THAT THE RISER INDICATES |
| | 3-6/0 CONDUCTORS FEEDING PANEL"B".SHOW |
| | ACTUAL SIZE.SEE SCHEDULE. |
| | |
| | 3} PLEASE NOTE FRONT AND REAR |
| | RECEPTS REQ`D PER 210.52E. |
| | |
| | 4} PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG. |
| | |
| | 5} PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2',6',12' RULE PER 210.52. |
| | SEE REVIEWED PLANS. |
| | |
| | 6} NOTE # 13 IN ELECTRICAL NOTES |
| | INCORRECTLY REFERS TO SLEEPING ROOM |
| | RECEPTACLES BEING ARC FAULT,PLEASE SEE |
| | 210.12 REFERS TO ALL BRANCH CIRCUITS. |
| | |
| | 7} PLEASE NOTE THAT THE 200 AMP EXISTING |
| | PANEL IS MARKED AS MLO AND SHOWN AS MCB |
| | ON THE RISER,PLEASE CORRELATE. |
| | |
| | 8} PLEASE SHOW THE LOCATION OF THE NEW |
| | A/C EQUIPMENT ON THE PLAN,AND THE |
| | LOCATION OF THE DISCONNECTS. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |