Plan Review Notes
Plan Review Notes For Permit 03110799
Permit Number 03110799
Review Stop P
Sequence Number 2
Notes
Date Text
2004-01-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) FROM PREVIOUS REVIEW: PLANS ROUTED TO
 THE DEPT. OF BUSINESS REGULATION HOTEL
 AND RESTURANT DIV. SHALL BE STAMPED BY
 THEIR REVIEWER AND WORK SHEETS FROM RE-
 VIEWER ATTACHED TO PLANS SUBMITTED FOR
 REVIEW AT CITY OF WPB.
 2) FROM PREVIOUS REVIEW: FOR GAS REVIEW.
 A. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 3) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER
 ON EACH SHEET. IF PRACTICING THORUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS, THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHOR-
 IZATION NUMBER OF THE ENGINEERING BUSIN-
 ESS ON EACH SHEET. 61G15-23.002(2) AND
 FS 471.
 4) SEE ATTACHED SHEET WITH STANDARD
 GREESE TRAP DETAIL APPROVED BY CITY OF
 WEST PALM BEACH. DETAIL ON SHEET P1.1
 NOT APPROVED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]